![salmson CC Скачать руководство пользователя страница 34](http://html2.mh-extra.com/html/salmson/cc/cc_installation-and-operating-instructions-manual_3598688034.webp)
34
ENGLISH
Table 2, Menue description
Menue-
No.
Display
Description
Parameter settings/
Functions
Factory-
settings
visible for
.
changeable by
User 1 and higher:
*
User 1 and higher:
*
Call
User 2 and higher:
**
User 2 and higher:
**
by:
Service:
***
Service:
***
0
Main menue
Display of operationmodes of
pumps and actual systempres-
sure valueCall of pumpsettings,
diagram and main menue
none
-
1
Pump 1...6
*
Call of operation mode setting,
operationdata and information
about pump 1...6 (number:
installation specific)In case of the
FC-operated pump actual val-
ues of current and frequency are
being displayed
none
-
1.1
Operation mode Pump
*
Adjustment of opeartionmode of
pumps: Hand (on line), Auto-
matic (on line or FC-driven -
depends on controller) or OFF
(no starting of pump via control)
Operation mode
**
Automatic
1.2
Operation data Pump
*
Display of overall running hours
(since commissioning) and run-
ning hours at the day, switching
actions (Number of "On"-switch-
ings)
none
-
1.3
Info Pump
*
Display of pump information:
Type, output power P
2
and nom-
inal current I
N
. Input of pump
data when commissioning, Data
will be copied from pump 1 to
pump 2...6
Pump type
Output power P
2
[kW]
Nominal current I
N
[A]
**
**
**
Installation
specific
2
0,00 bar
Diagram
*
Diagramm for displaying of sys-
tempressure and FC-frequency
values over time axisCall of trig-
gersettings and simulationmode
keine
-
2.1
Triggerein settings
*
Setting of time base (triggertime)
of diagram
Trigger time [s]
*
0 s