Table 1, Fault signals
If the problem cannot be rectified, contact your sanitation and
heating dealer or Salmson Customer Service.
Subject to technical alterations
Code
Alarmtext
Causes
Remedies
E20
FC Error
Frequency converter signals failure
Check failure display in menue
3.3.6 or on the FC-display, rectifica-
tion according to installation and
operation manual of FC
Elektrical connection defective
Check and, if required, maintain
electrical connections of FC
Motor protection of FC tripped
(e.g. short circuit of FC-mains;
Overload of pump)
Check and, if required, maintain
electrical supply line of FC (see
installation and operation manual
of pump)
E40
Sensor fault
Pressure sensor defective
Replace sensor
No electrical connection to sensor
Maintain electrical connections
E42
Pre-pressure min
Dry run protection tripped
Check inlet or storage tank; System
restarts automatically
E43
Output pressure Min
The output pressure of the system
has fallen below the value set in
menu 3.3.2.3 (e.g. because of
burst pipe)
Check whether set value complies
with local conditions
Check and, if required, repair
pipework
E44
Output pressure min
Output pressure of system below
value adjusted (e.g. caused by
pipe breakage) in menue 3.3.2.3
Check if adjustments meet require-
ments of local installation
Check and, if requested, maintain
pipework
E61
Pump1 Alarm
Winding overtemperature (WPC/
PTC)
Clean cooling fins; Motors are
designed for ambient tempera-
tures up to +40°C (see installation
and operation manual of pump)
E62
Pump2 Alarm
E63
Pump3 Alarm
E64
Pump4 Alarm
Motorprotection tripped (Overcur-
rent or short circuit in supply line)
Checking pump (see installation
and operation manual of pump)
and supply line connection
E65
Pump5 Alarm
E66
Pump6 Alarm
E88
E88 Battery discharged
The battery is discharged down to
minimal niveau, the further buffer-
ing of real time clock is any longer
assured
Replace battery (see chapter 9)