Do not clean the equipments with products that could have 

alcohol, benzene, solvent or other inflammable substances, 

or they are abrasive, corrosive, liquids or detergent.

• 

When it is needed to remove the protection cover to access 
to the terminals, they will have to be put back before starting 
up the equipment. Otherwise you may incur personal injury 
or equipment damage.

• 

Be careful to not lift heavy loads without help, according to 
the following recommendations:

 

ˆ

, < 18 kg.

 

ˆ



, 18 - 32 kg.

 

ˆ



, 32 - 55 kg.

 

ˆ

, > 55 kg.

• 

UPSs are electronic equipments, so they will be treated as 
they are:

 

ˆ

Avoid shocks.

 

ˆ

Avoid jolting or bouncing of the UPS, like those produced 

by moving the equipment on a hand truck and move on 

an uneven or wavy surface.

• 

UPS transport will be done packaged inside its original pack-
aging in order to prevent it from shock and impact and by 
means of the suitable type of packaging (carton box, pallet 
packaging, ...) and appropriate to its weight.

• 

Although the physical location of the elements can difer from 

the illustrations in this manual in some cases, the correct la-

belling correct the possible doubts and makes easy its com-
prenhension.

1.2.3.3.  Safety warning regarding batteries.

• 

The manipulation and connection of the batteries 

shall be done and supervised by 

personnel with 

battery knowledge only

.

Before doing any action, disconnect the batteries. Check that 

no current is present and there is not dangerous voltage in 

the DC BUS (capacitors) or in the endpoint of the battery set 

terminals.
Battery circuit is not isolated from input voltage. Dangerous 

voltages can be found between the terminals of the battery 

set and the earth. Check that there is not any voltage at the 

input before take any action over them.

• 

When faulty batteries are replaced, the complete battery set 

has to be replaced, less exceptional cases in new equip-

ments, were due to manufacturing faults it will only be re-

placed the defective ones.
The replacement will be done by another one of the same 

type, voltage, capacity, quantity and brand. All of them has to 

be of the same brand.

• 

Generally, the used batteries are sealed lead acid of 12V and 

maintenance free (VRLA).

• 

Do not reuse the faulty batteries. There could be an explo-

sion or burst any battery with the involved problems and is-

sues that could happen.

• 

Generally supplied batteries are installed in the same cab-

inet, case or rack of the equipment. Depending on the power, 

autonomy or both, they can be supplied separately from the 

equipment in another cabinet, case or rack, with the interlink 

cables among them. Do not modify its length.

• 

In those equipments requested without batteries, their ac-

quisition, installation and connection of themselves will be 

done by the end-user and 

under his responsibility

. Data 

concerning the batteries as regards to quantity, capacity and 

voltage, are stated in this battery label sticked beside the 

nameplate of the equipment. 

Respect these data

, battery 

connection polarity and the supplied circuit diagram 

strictly

.

For an optimum and efficient operating, the battery set has to 

be located as close as possible to the equipment.

• 

The battery voltage can involve the risk of electric 

shock and can produce high short circuit currents. 

Observe the following preventive measures before manipu-

lating any terminal block identified in the labelling as «Bat-

teries»:

 

ˆ

Disconnect the corresponding protection elements.

 

ˆ

When connecting a battery cabinet to the equipment, 

respect the cable’s polarity and colour (red-positive; 

black-negative) indicated in the manual and in the cor-

responding labelling.

 

ˆ

Wear rubber gloves and shoes.

 

ˆ

Use tools with insulated handles.

 

ˆ

Take off watches, rings or other metal objects.

 

ˆ

Do not place metal tools or objects over the batteries.

 

ˆ

Never manipulate with your hands or through conducting 

objects, do not short either the battery terminal block of 

the equipment or the own from the batteries.

• 

In order to avoid a complete discharge of the batteries and 

as a safety measure after a long blackout of the commercial 

mains and when ending the working day, proceed to the load 

shutdown and then to the equipment too, by following the op-

erating described in this «User's manual».

• 

When the equipment and/or battery module has a protec-
tion through a fuse and it were needed to be replaced, it will 
always be done by another one with the same dimension, 
type and size.

• 

For long periods of disconnection, consider that the 

equipment has to be connected once a month for 10 hours as 

minimum, in order to charge the batteries, so the irreversible 

degradation of itself is avoided. On the other hand, in case of 

storing an equipment, it will be done in a fresh and dry place, 

never outdoors

.

• 

Never short the battery terminals as it involves a high risk. It 

involves the detriment of the equipment and batteries.

• 

Avoid mechanical efforts and impacts.

• 

Do not open or mutilate the battery. Spilled electrolyte is 

harmful and toxic to the skin and eyes.

• 

Do not dispose the batteries in a fire and high temperatures. 

The batteries may explode.

• 

In case of contact of the acid with parts of the body, wash 

immediately with plenty water and call urgently the nearest 

medical service.

• 

Batteries involve a serious risk for the health and for the en-

vironment. Their disposal should be done according to the 

existing laws.

Содержание SLC TWIN PRO Series

Страница 1: ...PS LIGHTING FLOW DIMMER STABILIZERS ILUEST SWITCH MODE POWER SUPPLY STATIC INVERTERS PHOTOVOLTAIC INVERTERS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS UPSSLCTWINPROseries 4 to 20 kVA UNINTERRUPTI...

Страница 2: ......

Страница 3: ...ing 5 1 Commissioning 5 1 1 Controls before commissioning 5 2 Start up and shutdown of the UPS 5 2 1 Start up of the UPS with mains present 5 2 2 Start up of the UPS without mains 5 2 3 UPS shutdown w...

Страница 4: ...structions for safety of the things To not respect such instructions can damage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instru...

Страница 5: ...chnical Regulations or standards of the country Use approved cables only Protection Earth cable of the UPS drives the leakage current of the load devices An isolated earth cable has to be installed as...

Страница 6: ...r cause can make an electrical discharge of high voltage and it is restricted to qualified staff only Do not open the equipment A part from the implicit stated risks any action that make the modificat...

Страница 7: ...hem Do not modify its length In those equipments requested without batteries their ac quisition installation and connection of themselves will be done by the end user and under his responsibility Data...

Страница 8: ...ive EMC In accordance with the specifications of the harmonized stand ards Standards as reference EN IEC 62040 1 Uninterruptible power supply UPS Part 1 1 General and safety requirements for UPS s use...

Страница 9: ...due to the constant evolution of the product some discrepancies or small contradictions can arise In front of any doubt the labelling of the equipment will always prevail i Figures regarding its main...

Страница 10: ...USB Protection cover for external batteries IEC output connectors Protection cover for manual bypass switch maintenance and output Protection cover for power blocks USB RS 232 EPO Protection cover for...

Страница 11: ...11 SALICRU Battery switch Protection cover for power blocks Batteries module for models 10 kVA Batteries module for models up to 10 kVA Battery switch Power blocks Fig 3 Rear view batteries module...

Страница 12: ...ews and electrical cables Batteries owned by the client will be installed out from the case or cabinet of the UPS Under request it is possible to supply the acces sories screws and electrical cables n...

Страница 13: ...user s installation wiring is achieved as well as low input current distortion so mains pollution is decreased Great adaptability to the worst conditions of the input mains Wide margins of the input v...

Страница 14: ...tor The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of controlling and management at the manager system dis posal This facili...

Страница 15: ...es type B for RCD devices and C characteristic for circuit breakers For the output load feeding C characteristic for circuit breaker Regarding the size they will be as minimum to the cur rents stated...

Страница 16: ...any start it up according to the instructions described in this manual and charge them for 2 hours from floating level In parallel systems it is not needed to make the connection among the equipments...

Страница 17: ...all ends of the cables connected to the power blocks input output and by pass Check the correct torque in the screws of the power blocks In installations with only one UPS the Jumper cable as bridge...

Страница 18: ...is done through the terminals of the own UPS MC coil out and MC coil in R N R S T N R N U N 1 3 2 SAI Backfeed protection connection in TWIN 3 PRO 10 kVA Backfeed protection signal Backfeed protectio...

Страница 19: ...wn in any of the machines connected to the device causing a short circuit it will affect to no more than the line that is faulty The rest of the connected loads will have their continuity as sured due...

Страница 20: ...of each equipment with its external battery cabinet s has to be done like if they were single units completely separate from the rest ones Each battery module is independent for each equip ment It is...

Страница 21: ...tput static bypass this last one for TWIN 3 PRO 10 kVA models only also a manual bypass with mechanical lock see figures 12 and 13 This switchgear panel allows isolating only one equipment from the sy...

Страница 22: ...oltage circuit of safety To preserve the quality it has to be installed separate from other lines that have dangerous voltages energy distribution line UPS has a dry contact card for the relays interf...

Страница 23: ...imum before using the UPS for first time For models with single phase input TWIN PRO or three phase TWIN 3 PRO up to 10 kVA It will be necessary to supply power supply voltage to the equipment and tur...

Страница 24: ...attery switch is in position On models B0 and B1 Turn the input M1 and bypass M2 circuit breakers to On Switch M2 is only available in models TWIN 3 PRO 10 kVA In equipments with single phase input TW...

Страница 25: ...will transfer to Bypass mode Put all the equipments on manual bypass To do it re move the cover from manual bypass switch which is located at the back of each equipment and turn all the switches to p...

Страница 26: ...he UPSs have to be set contact with the S T S Press over the shutdown key in any UPS for more than 3 seconds and each one will be shutdown supplying output voltage through the bypass Turn On the outpu...

Страница 27: ...ot be fed Turn the manual bypass switch of the panel to Off UPS and put the mechanical lock To avoid wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed t...

Страница 28: ...g Press the key for 1 sec as minimum to validate the modified option and change the settings Table 6 Functionality of the buttons or keypad of the control panel The UPS has a control panel with the fo...

Страница 29: ...TWIN Blue 72 Warning On maintain Bypass UPS only 8 20 kVA TWIN 3 Blue Code Condition Description Color LCD 81 Fault Heatsink over temperature Red 82 Alarm Ambient over temperature UPS only 4 10 kVA TW...

Страница 30: ...ad level connected to the UPS UPS power supply information three phase input UPS output information Equipment Battery information Fig 18 Main screen of the equipment with three phase input All the scr...

Страница 31: ...supply fails due to fault or wrong the equipment will transfer to Battery mode to feed the load s properly Fig 24 Frequency converter mode screen This function can be activated through the settings of...

Страница 32: ...ucture of the main menu includes six submenus UPS status Event log Measurement Control Identification Setting With password only and by the S T S 6 3 2 UPS status submenu When pressing the key for les...

Страница 33: ...ucture of UPS status menu Structure of main menu Press 1 sec Fig 31 UPS status screen Press 1 sec Press o 1 sec Structure of Data logger submenu Structure of main menu Press 1 sec Fig 32 Event logger...

Страница 34: ...rd only Fig 34 Control submenu screens 6 3 5 Control submenu When pressing the key the key for less than 1 sec from this Control submenu it is accessed to the control structure see figure 34 Shutdown...

Страница 35: ...ndard configuration from factory 6 4 1 Operating on ECO mode 6 4 1 1 Short description of the ECO mode ECO mode function allows supplying the load s from mains directly through the internal filters on...

Страница 36: ...en used for long time In hot areas battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years 25 C In ca...

Страница 37: ...the UPS cooling and the ambient temperature of the room NTC abnormal UPS internal fault Consult with the S T S Communication cable male disconnected Para cable Male Loss Alarm code E3 Parallel bus ca...

Страница 38: ...oltage Inv Under Voltage Alarm code 33 UPS internal fault Consult with the S T S Inverter Softstart Failed Inv Softstart Fail Alarm code E34 UPS internal fault Consult with the S T S Negative Power Fa...

Страница 39: ...7 3 1 Covered product UPS SLC TWIN PRO series 7 3 2 Warranty terms This product is guaranteed against any parts and or labour defect for 12 months period from its commissioning by our company staff o...

Страница 40: ...age THD with non linear load 5 Output voltage recovering time 100 ms IEC 62040 3 70 ms IEC 62040 3 60 ms IEC 62040 3 Transient response of the output voltage with load fluctuation of 0 100 0 9 7 7 Tra...

Страница 41: ...elation to the working height 8 2 Glossary AC It is nominated as alternating current abbreviation in Spanish CA and in English AC to the electrical current in which the magnitude and direction varies...

Страница 42: ...rcuit when it over comes the maximum set values On Line mode Regarding to an equipment it is on line when it is connected to the system and it is in operation and usually has its power supply turned o...

Страница 43: ...43 SALICRU...

Страница 44: ...NCIA VALLADOLID ZARAGOZA BRANCHES AND SERVICES AND TECHNICAL SUPPORT S T S CHINA FRANCIA HUNGR A MARRUECOS M XICO PORTUGAL REINO UNIDO SINGAPUR SUBSIDIARIES ALEMANIA ARABIA SAUD ARGELIA ARGENTINA B LG...

Отзывы: