background image

25

SALICRU

5.3.  Operative for a parallel system.

• 

The following operative, it is considered for equipments with 

the configuration preset from factory.

• 

Check that the load/s and output circuit breakers switches 

from protection panel, are in position "Off". 

• 

Turn "On" the following circuit breaker switches:

 

ˆ

All the input switches from protection panel.

 

ˆ

The input ones of each UPS.

 

ˆ

In equipments with static bypass line (

TWIN/3 PRO

 > 10 

kVA), the bypass ones from protection panel.

 

ˆ

In equipments with static bypass line (

TWIN/3 PRO

 > 10 

kVA), the bypass ones of each UPS.

UPSs supply output voltage through the bypass. Check the 

LCD from control panel, in case there was any warning or 

error information. Check the output voltage at the power 

blocks of each UPS separately, in order to check the voltage 

difference is below 1V among them. If the difference is higher 

than 1 V, double check the wiring and associated instruc-

tions.

• 

Press over the start up key   for more than 1 second in any 

of the UPSs and all of them will start up. All UPSs will transfer 

to "Normal mode”.
Measure the output voltage on each UPS separately, to 

check the voltage difference is under 0,5 V. In case the differ-

ence were higher than 1 V, the UPSs have to be set (contact 

with the 

S.T.S.

).

• 

Press over the start up key   for more than 3 seconds in any 

UPS and all of them will be shutdown, at the output will be 

voltage supplied through the bypass.
Turn “On” the output circuit breaker switches from the dis-

tribution panel and the complete parallel system will supply 

output voltage through the bypass.

• 

Press over the start up key   for more than 1 second in any 

of the UPSs and all of them will start up., finally the parallel 

system will be working on "Normal mode” 

• 

Start up the load/s.

5.4.  How to integrate a new UPS in an 

operating parallel system.

• 

The descriptions hereby detailed are referred to the inte-

gration of one equipment. For two equipments, the tasks to 

make are the same less the quantity of units and connec-

tions. Proceed accordingly.

• 

Attend the instructions stated in section 4.3.7.2, for parallel 
connection.

• 

Protection panel must have the corresponding input, output 

and static bypass switches (the last one in 

TWIN/3 PRO

 > 10 

kVA version only), and also the manual bypass.

• 

Due to it is needed to modify the own parallel bus con-

nection, in order to integrate the new equipment into the 

system (wiring bundle with DB25 connectors), the load 

feeding will have to be transferred to manual bypass. 
Proceed as follows:

 

ˆ

Press over the key   in any UPS for more than 3 sec-

onds to shutdown all the inverters. The acoustic alarm 

will beep for 3 seconds. The equipments that belong to 

the current parallel system will transfer to "Bypass mode".

 

ˆ

Put all the equipments on manual bypass. To do it re-

move the cover from manual bypass switch, which is 

located at the back of each equipment and turn all the 

switches to position "BYPASS".

 

ˆ

 

Keep in mind that on "Bypass mode" or with the 

switch on position "BYPASS", the loads will be 

exposed to fluctuations of voltage, frequency and mains 

faults or blackouts, so in case it were possible choose 

one day with the lowest probability of faults (days without 

fluctuations, days without storms,... ) and do it as fast as 

possible.

 

ˆ

Turn the input and bypass circuit breaker protections 

(

TWIN/3 PRO

 > 10 kVA) of each equipment to "Off".

 

ˆ

Turn "Off" the output circuit breaker of the protection 

panel, corresponding to the new UPS to be integrated.

 

ˆ

Disconnect the communication bus between the first and 

last equipment, and reconnect it including the new UPS. 

It is essential to close the bus loop to have a good opera-

tion.

• 

Turn "On" the following circuit breaker switches:

 

ˆ

Each one from the input of each UPS.

 

ˆ

In those equipments with static bypass line (

TWIN/3 PRO

 

> 10 kVA), also the bypass ones of each UPS.

UPSs supply output voltage from bypass. Check the screen 

of the LCD from control panel in case there were any warning 

or error information.
Measure the output voltage in the power blocks of the parallel 

system and in the output terminals of the new UPS, check 

the voltage difference is below 1 V. In case the difference 

were higher than 1 V, double check the wiring and associated 

instructions.

• 

Put back the cover of the manual bypass of each UPS.

• 

Press over the start up key   for more than 1 second in any 

of the UPSs and all of them will start up. All UPSs will transfer 

to "Normal mode”. 
Measure the output voltage between the terminals 

JP1

 of the 

parallel system and terminals 

JP1

 of the new UPS, to check 

the voltage difference is under 0,5 V. In case the difference 

were higher than 1 V, the UPSs have to be set (contact with 

the 

S.T.S.

)

• 

Press over the shutdown key   in any UPS for more than 

3 seconds and each one will be shutdown, supplying output 

voltage through the bypass.
Turn “On” the output circuit breaker switch of the distribution 

panel, corresponding to the new integrated equipment. The 

complete parallel system will supply output voltage, through 

the bypass.

• 

Remove the cover of the manual bypass in each UPS.

• 

Transfer the equipments with the manual bypass ("BYPASS" 

position) to position "UPS". Do it in the switches of all equip-

ments.

• 

Put back the protection cover of the manual bypass 

switch of all equipments, also check the torque of the 

fixing screws, otherwise any of the limit contacts could be 

activated and the manual bypass too.

• 

Press over the start up key   for more than 1 second in any 

of the UPSs and all of them will start up, finally the parallel 

system will be working on "Normal mode”.
Load/s are protected by the parallel system again.

Содержание SLC TWIN PRO Series

Страница 1: ...PS LIGHTING FLOW DIMMER STABILIZERS ILUEST SWITCH MODE POWER SUPPLY STATIC INVERTERS PHOTOVOLTAIC INVERTERS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS UPSSLCTWINPROseries 4 to 20 kVA UNINTERRUPTI...

Страница 2: ......

Страница 3: ...ing 5 1 Commissioning 5 1 1 Controls before commissioning 5 2 Start up and shutdown of the UPS 5 2 1 Start up of the UPS with mains present 5 2 2 Start up of the UPS without mains 5 2 3 UPS shutdown w...

Страница 4: ...structions for safety of the things To not respect such instructions can damage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instru...

Страница 5: ...chnical Regulations or standards of the country Use approved cables only Protection Earth cable of the UPS drives the leakage current of the load devices An isolated earth cable has to be installed as...

Страница 6: ...r cause can make an electrical discharge of high voltage and it is restricted to qualified staff only Do not open the equipment A part from the implicit stated risks any action that make the modificat...

Страница 7: ...hem Do not modify its length In those equipments requested without batteries their ac quisition installation and connection of themselves will be done by the end user and under his responsibility Data...

Страница 8: ...ive EMC In accordance with the specifications of the harmonized stand ards Standards as reference EN IEC 62040 1 Uninterruptible power supply UPS Part 1 1 General and safety requirements for UPS s use...

Страница 9: ...due to the constant evolution of the product some discrepancies or small contradictions can arise In front of any doubt the labelling of the equipment will always prevail i Figures regarding its main...

Страница 10: ...USB Protection cover for external batteries IEC output connectors Protection cover for manual bypass switch maintenance and output Protection cover for power blocks USB RS 232 EPO Protection cover for...

Страница 11: ...11 SALICRU Battery switch Protection cover for power blocks Batteries module for models 10 kVA Batteries module for models up to 10 kVA Battery switch Power blocks Fig 3 Rear view batteries module...

Страница 12: ...ews and electrical cables Batteries owned by the client will be installed out from the case or cabinet of the UPS Under request it is possible to supply the acces sories screws and electrical cables n...

Страница 13: ...user s installation wiring is achieved as well as low input current distortion so mains pollution is decreased Great adaptability to the worst conditions of the input mains Wide margins of the input v...

Страница 14: ...tor The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of controlling and management at the manager system dis posal This facili...

Страница 15: ...es type B for RCD devices and C characteristic for circuit breakers For the output load feeding C characteristic for circuit breaker Regarding the size they will be as minimum to the cur rents stated...

Страница 16: ...any start it up according to the instructions described in this manual and charge them for 2 hours from floating level In parallel systems it is not needed to make the connection among the equipments...

Страница 17: ...all ends of the cables connected to the power blocks input output and by pass Check the correct torque in the screws of the power blocks In installations with only one UPS the Jumper cable as bridge...

Страница 18: ...is done through the terminals of the own UPS MC coil out and MC coil in R N R S T N R N U N 1 3 2 SAI Backfeed protection connection in TWIN 3 PRO 10 kVA Backfeed protection signal Backfeed protectio...

Страница 19: ...wn in any of the machines connected to the device causing a short circuit it will affect to no more than the line that is faulty The rest of the connected loads will have their continuity as sured due...

Страница 20: ...of each equipment with its external battery cabinet s has to be done like if they were single units completely separate from the rest ones Each battery module is independent for each equip ment It is...

Страница 21: ...tput static bypass this last one for TWIN 3 PRO 10 kVA models only also a manual bypass with mechanical lock see figures 12 and 13 This switchgear panel allows isolating only one equipment from the sy...

Страница 22: ...oltage circuit of safety To preserve the quality it has to be installed separate from other lines that have dangerous voltages energy distribution line UPS has a dry contact card for the relays interf...

Страница 23: ...imum before using the UPS for first time For models with single phase input TWIN PRO or three phase TWIN 3 PRO up to 10 kVA It will be necessary to supply power supply voltage to the equipment and tur...

Страница 24: ...attery switch is in position On models B0 and B1 Turn the input M1 and bypass M2 circuit breakers to On Switch M2 is only available in models TWIN 3 PRO 10 kVA In equipments with single phase input TW...

Страница 25: ...will transfer to Bypass mode Put all the equipments on manual bypass To do it re move the cover from manual bypass switch which is located at the back of each equipment and turn all the switches to p...

Страница 26: ...he UPSs have to be set contact with the S T S Press over the shutdown key in any UPS for more than 3 seconds and each one will be shutdown supplying output voltage through the bypass Turn On the outpu...

Страница 27: ...ot be fed Turn the manual bypass switch of the panel to Off UPS and put the mechanical lock To avoid wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed t...

Страница 28: ...g Press the key for 1 sec as minimum to validate the modified option and change the settings Table 6 Functionality of the buttons or keypad of the control panel The UPS has a control panel with the fo...

Страница 29: ...TWIN Blue 72 Warning On maintain Bypass UPS only 8 20 kVA TWIN 3 Blue Code Condition Description Color LCD 81 Fault Heatsink over temperature Red 82 Alarm Ambient over temperature UPS only 4 10 kVA TW...

Страница 30: ...ad level connected to the UPS UPS power supply information three phase input UPS output information Equipment Battery information Fig 18 Main screen of the equipment with three phase input All the scr...

Страница 31: ...supply fails due to fault or wrong the equipment will transfer to Battery mode to feed the load s properly Fig 24 Frequency converter mode screen This function can be activated through the settings of...

Страница 32: ...ucture of the main menu includes six submenus UPS status Event log Measurement Control Identification Setting With password only and by the S T S 6 3 2 UPS status submenu When pressing the key for les...

Страница 33: ...ucture of UPS status menu Structure of main menu Press 1 sec Fig 31 UPS status screen Press 1 sec Press o 1 sec Structure of Data logger submenu Structure of main menu Press 1 sec Fig 32 Event logger...

Страница 34: ...rd only Fig 34 Control submenu screens 6 3 5 Control submenu When pressing the key the key for less than 1 sec from this Control submenu it is accessed to the control structure see figure 34 Shutdown...

Страница 35: ...ndard configuration from factory 6 4 1 Operating on ECO mode 6 4 1 1 Short description of the ECO mode ECO mode function allows supplying the load s from mains directly through the internal filters on...

Страница 36: ...en used for long time In hot areas battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years 25 C In ca...

Страница 37: ...the UPS cooling and the ambient temperature of the room NTC abnormal UPS internal fault Consult with the S T S Communication cable male disconnected Para cable Male Loss Alarm code E3 Parallel bus ca...

Страница 38: ...oltage Inv Under Voltage Alarm code 33 UPS internal fault Consult with the S T S Inverter Softstart Failed Inv Softstart Fail Alarm code E34 UPS internal fault Consult with the S T S Negative Power Fa...

Страница 39: ...7 3 1 Covered product UPS SLC TWIN PRO series 7 3 2 Warranty terms This product is guaranteed against any parts and or labour defect for 12 months period from its commissioning by our company staff o...

Страница 40: ...age THD with non linear load 5 Output voltage recovering time 100 ms IEC 62040 3 70 ms IEC 62040 3 60 ms IEC 62040 3 Transient response of the output voltage with load fluctuation of 0 100 0 9 7 7 Tra...

Страница 41: ...elation to the working height 8 2 Glossary AC It is nominated as alternating current abbreviation in Spanish CA and in English AC to the electrical current in which the magnitude and direction varies...

Страница 42: ...rcuit when it over comes the maximum set values On Line mode Regarding to an equipment it is on line when it is connected to the system and it is in operation and usually has its power supply turned o...

Страница 43: ...43 SALICRU...

Страница 44: ...NCIA VALLADOLID ZARAGOZA BRANCHES AND SERVICES AND TECHNICAL SUPPORT S T S CHINA FRANCIA HUNGR A MARRUECOS M XICO PORTUGAL REINO UNIDO SINGAPUR SUBSIDIARIES ALEMANIA ARABIA SAUD ARGELIA ARGENTINA B LG...

Отзывы: