8.1. General technical specifications.
Models:
TWIN PRO
TWIN/3 PRO
≤
10 kVA
TWIN/3 PRO > 10 kVA
Available powers (kVA / kW)
4 / 3.6
5 / 4.5
6 / 5.4
8 / 7.2
10 / 9
8 / 7.2
10 / 9
12 / 10.8 15 / 13.5
20 / 18
Technology
On-line double conversion, PFC, double DC bus
Rectifier
Tipology of the input
Single phase
Three phase
Quantity of wires
3 wires - Phase R(L) + Neutral (N) and earth
5 wires - 3 phases R(L1), S(L2), T(L3) + Neutral (N) amd earth
Nominal voltage
208 / 220 / 230 / 240 V AC
3 x 380 / 3 x 400 / 3 x 415 V AC
Input voltage range with 100 % load
176÷276 V AC
3 x 305÷478 V AC
Input voltage range with 50 % load
110÷276 V AC
3 x 190÷478 V AC
Voltage range of transference:
Depending on the load percentage between 100 and 50 %
- Low mains voltage
176 / 110 V AC (±3 %)
305 / 190 V AC (± 3 %)
- Restore from low mains
186 / 120 V AC (±3 %)
322 / 208 V AC (± 3 %)
- High mains voltage
276 V AC (±3 %)
478 V AC (± 3 %)
- Restore from mains high
266 V AC (±3 %)
461 V AC (± 3 %)
Frequency
50 / 60 Hz (autosensing)
Input frequency range
± 10 % (45-55 / 54-66 Hz)
THDi
< 5 % at full load
Power factor
> 0,99 (at full load)
Inverter
Technology
PWM
Switching frequency
19.2 kHz
Wave shape
Pure sinewave
Nominal voltage
208 / 220 / 230 / 240 V AC
3 x 380 / 3 x 400 / 3 x 415 V AC
Output voltage accuracy
± 1 %
Voltage THD with linear load
< 2 %
Voltage THD with non-linear load
< 5 %
Output voltage recovering time
100 ms. (IEC 62040-3)
70 ms. (IEC 62040-3)
60 ms. (IEC 62040-3)
Transient response of the output voltage (with
load fluctuation of 0 %-100 %-0 %)
± 9 %
≤ 7 %
≤ 7 %
Transient response of the output voltage (with
load fluctuation of 20 %-100 %-20 %)
± 6 %
≤ 4 %
≤ 4 %
Frequency
With mains present, synchronised at nominal input (45-55 / 54-66 Hz)
Free running, back up time mode 50 / 60 ±0.1 Hz
Free running, back up time mode 50 / 60 ±0.05 Hz
Slew rate
1 Hz/sec.
< 1 Hz/sec.
1 Hz/sec.
Power factor
0.9 (by default)
0.5 to 1
Permissible load power factor
0.3 to 1 inductive
Transfer time, inverter to battery
0 ms.
Transfer time, inverter to bypass
0 ms.
Transfer time, inverter to ECO
0 ms.
Transfer time, ECO to inverter
< 10 ms.
Efficiency at full load, line mode with 100%
charged battery
> 92 %
> 93 %
> 94 %
Efficiency at full load, on battery mode
> 92 %
> 93 %
> 94 %
Efficiency at full load, on ECO mode
> 97 %
> 97 %
> 98 %
Overload, line mode
105-125 %, 2 min.
100-110 %, 5 min.
110-130 % , 1 min.
130-150 %, 10 sec.
> 150 %, 2 sec.
100-110 %, 5 min.
125-150 %, 30 sec.
110-130 %, 1 min.
> 150 %, 1 sec.
130-150 %, 10 sec.
-
> 150 %, 2 sec.
Overload, battery mode
102-130 %, 10 sec.
105-125 %, 2 min.
100-110 %, 5 min.
> 130 %, 100 ms
125-150 %, 30 sec.
110-130 %, 1 min.
-
-
130-150 %, 10 sec.
-
-
> 150 %, 2 sec.
Crest factor
3:1
maximum, 3:1
3:1
Quantity of equipments in parallel connection
Up to 4 SAI’s
Static bypass
Type
Hybrid (thyristors in antipa relay)
Nominal voltage
208 / 220 / 230 / 240 V
Nominal frequency
50 / 60 Hz ±4 Hz