Salicru SLC TWIN PRO Series Скачать руководство пользователя страница 15

15

SALICRU

4.  Installation.

• 

Check the Safety instructions, from section 1.2.3.

• 

Check that the data in the nameplate are the required by the 

installation.

• 

A wrong connection or manoeuvring, can make faults in the 

UPS and/or loads connected to itself. Read carefully the in-

structions of this manual and follow the stated steps in the 

established order.

• 

This UPS has to be installed by qualified staff and it 

can be used by personnel with no specific training, 

just with the help of this «Manual» only.

• 

All connections of the equipment including the control 

(interface, remote panel, ...), will be done with the 

switches at rest and no voltage present (UPS power supply 

switch to «Off»).

• 

Never forget that the UPS is an electrical energy gener-

ator, so the user has to take the needed cautions against 

direct and indirect contacts.

• 

When there is only one equipment, omit all the instructions 

and their implicit connections as regards to parallel systems.

• 

Parallel system installation needs a switchgear panel with 

input, output and static bypass single protections (the last 

one for 

TWIN/3 PRO

 models higher than 10 kVA only), and a 

manual bypass too.
This switchgear panel allows isolating only one equipment 

from the system, when facing any malfunctioning and sup-

plying the loads with the rest of equipments during the pre-

ventive maintenance or during the reparation of itself.
Under request a manual bypass panel can be supplied for a 

single equipment or a particular system.

• 

In parallel systems, the length and cross section of the 

cables that go from the switchgear panel till one of the 

UPSs and vice versa, will be the same for all of them without 

any exception.

• 

Battery circuit is not isolated from input voltage. Haz-

ardous voltages can be found out between the battery 

terminals and earth. Check that there is not input voltage be-

fore doing any intervention on them.

4.1.  To be considered in the installation.

• 

All the equipments and battery sets have terminals as con-

nection parts for power and connectors for communications.

• 

Terminals for separate bypass line are only available in 

TWIN/3 

PRO

 models higher than 10 kVA.

• 

Cross cable section of the input and output lines, will be cal-

culated from the currents stated in the nameplate of each 

equipment, and respecting the Local and/or National Low 

Voltage Electrotechnical Regulations.
For the bypass current stated in the nameplate, has to be 

considered two groups of equipments:

 

ˆ

Equipments up to 10 kVA 

TWIN/3 PRO

. Current on 

phase R is higher to the other two, because the input of 

the UPS is common with the bypass line. 

 

ˆ

Equipments > 10 kVA 

TWIN/3 PRO

. These equipments 

have separate terminals for UPS input and bypass line.

• 

Protections of the switchgear panel, will have the following 

features:

 

ˆ

For input and bypass lines, type B for RCD devices and 

C characteristic for circuit breakers.

 

ˆ

For the output (load feeding), C characteristic for circuit 

breaker.

Regarding the size, they will be as minimum to the cur-

rents stated in the nameplate of each UPS. Pay attention to 

the UPSs up to 10 kVA and three phase input, because a 

four pole switch has to be fitted in as input protection and a 

second one of two poles between this one and the own UPS, 

in order to protect the phase R and neutral.

• 

In the nameplate of the equipment there are only printed the 

nominal currents as it is stated in the safety standard EN-IEC 

62040-1. To calculate the input current, the power factor and 

the efficiency of the equipment have been considered.
Overload conditions are considered as nonpermanent and 

exceptional operating mode.

• 

 If it is added peripherals to the input, output or bypass like trans-

formers or autotransformers to the UPS, the currents stated in 

the own nameplates of those elements has to be considered 

in order to use the suitable cross sections, by respecting the 

Local and/or National Low Voltage Regulation 

• 

When an equipment incorporates a galvanic isolation 

transformer, as standard, as an option or either in-

stalled by yourself, either at the UPS input, bypass line, 

output or at all of them, protections against indirect contact 

has to be fitted in (residual current device) at the output of 

each transformer, because due to its specification of isolation 

it will prevent the triggering of the protections fitted in the pri-

mary of the transformer in case of electrical shock in the sec-

ondary (output of the isolation transformer) 

• 

 Remind you that all external isolation transformers already 

installed or supplied from factory, has the neutral of the sec-

ondary connected to earth by means of a cable bridge be-

tween both terminals. If it were required an isolated output 

neutral, remove this cable bridge, keeping the precautions 

stated in the respective local and/or national low voltage reg-

ulations.

• 

All standard UPSs have batteries in the same enclosure of 

the equipment , less those ones as B0 and B1. In the first 

ones, the battery protection is by internal fuses and there is 

no access to the end-user.
Accumulator cabinet or modules have battery protection 

too, and in this case, they are duplicated. An internal ones 

through fuses with no access for the end-user and an addi-

tional ones by means of a two pole circuit breaker.

• 

IMPORTANT FOR SAFETY: In case of installing the 

batteries by yourself, the accumulators have to be pro-

vided with a two pole circuit breaker protection sized to the 
features stated in table 2.

4.2.  Reception of the equipment.

4.2.1.  Unpacking, content checking and 

inspection.

• 

 To unpacking, see section 4.2.3.

• 

On receiving the device, make sure that it has not suffered 

any damage in transport (impact, drop, ...) and its features 

correspond with the ones in the order, so it is recommended 

to unpack the UPS and make a first visual inspection.

Содержание SLC TWIN PRO Series

Страница 1: ...PS LIGHTING FLOW DIMMER STABILIZERS ILUEST SWITCH MODE POWER SUPPLY STATIC INVERTERS PHOTOVOLTAIC INVERTERS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS UPSSLCTWINPROseries 4 to 20 kVA UNINTERRUPTI...

Страница 2: ......

Страница 3: ...ing 5 1 Commissioning 5 1 1 Controls before commissioning 5 2 Start up and shutdown of the UPS 5 2 1 Start up of the UPS with mains present 5 2 2 Start up of the UPS without mains 5 2 3 UPS shutdown w...

Страница 4: ...structions for safety of the things To not respect such instructions can damage the goods Precaution symbol Read the paragraph text and take the stated preventive mediums it contents the basic instru...

Страница 5: ...chnical Regulations or standards of the country Use approved cables only Protection Earth cable of the UPS drives the leakage current of the load devices An isolated earth cable has to be installed as...

Страница 6: ...r cause can make an electrical discharge of high voltage and it is restricted to qualified staff only Do not open the equipment A part from the implicit stated risks any action that make the modificat...

Страница 7: ...hem Do not modify its length In those equipments requested without batteries their ac quisition installation and connection of themselves will be done by the end user and under his responsibility Data...

Страница 8: ...ive EMC In accordance with the specifications of the harmonized stand ards Standards as reference EN IEC 62040 1 Uninterruptible power supply UPS Part 1 1 General and safety requirements for UPS s use...

Страница 9: ...due to the constant evolution of the product some discrepancies or small contradictions can arise In front of any doubt the labelling of the equipment will always prevail i Figures regarding its main...

Страница 10: ...USB Protection cover for external batteries IEC output connectors Protection cover for manual bypass switch maintenance and output Protection cover for power blocks USB RS 232 EPO Protection cover for...

Страница 11: ...11 SALICRU Battery switch Protection cover for power blocks Batteries module for models 10 kVA Batteries module for models up to 10 kVA Battery switch Power blocks Fig 3 Rear view batteries module...

Страница 12: ...ews and electrical cables Batteries owned by the client will be installed out from the case or cabinet of the UPS Under request it is possible to supply the acces sories screws and electrical cables n...

Страница 13: ...user s installation wiring is achieved as well as low input current distortion so mains pollution is decreased Great adaptability to the worst conditions of the input mains Wide margins of the input v...

Страница 14: ...tor The big IT systems based on LANs and WANs that integrate servers with different platforms they have to include an easy way of controlling and management at the manager system dis posal This facili...

Страница 15: ...es type B for RCD devices and C characteristic for circuit breakers For the output load feeding C characteristic for circuit breaker Regarding the size they will be as minimum to the cur rents stated...

Страница 16: ...any start it up according to the instructions described in this manual and charge them for 2 hours from floating level In parallel systems it is not needed to make the connection among the equipments...

Страница 17: ...all ends of the cables connected to the power blocks input output and by pass Check the correct torque in the screws of the power blocks In installations with only one UPS the Jumper cable as bridge...

Страница 18: ...is done through the terminals of the own UPS MC coil out and MC coil in R N R S T N R N U N 1 3 2 SAI Backfeed protection connection in TWIN 3 PRO 10 kVA Backfeed protection signal Backfeed protectio...

Страница 19: ...wn in any of the machines connected to the device causing a short circuit it will affect to no more than the line that is faulty The rest of the connected loads will have their continuity as sured due...

Страница 20: ...of each equipment with its external battery cabinet s has to be done like if they were single units completely separate from the rest ones Each battery module is independent for each equip ment It is...

Страница 21: ...tput static bypass this last one for TWIN 3 PRO 10 kVA models only also a manual bypass with mechanical lock see figures 12 and 13 This switchgear panel allows isolating only one equipment from the sy...

Страница 22: ...oltage circuit of safety To preserve the quality it has to be installed separate from other lines that have dangerous voltages energy distribution line UPS has a dry contact card for the relays interf...

Страница 23: ...imum before using the UPS for first time For models with single phase input TWIN PRO or three phase TWIN 3 PRO up to 10 kVA It will be necessary to supply power supply voltage to the equipment and tur...

Страница 24: ...attery switch is in position On models B0 and B1 Turn the input M1 and bypass M2 circuit breakers to On Switch M2 is only available in models TWIN 3 PRO 10 kVA In equipments with single phase input TW...

Страница 25: ...will transfer to Bypass mode Put all the equipments on manual bypass To do it re move the cover from manual bypass switch which is located at the back of each equipment and turn all the switches to p...

Страница 26: ...he UPSs have to be set contact with the S T S Press over the shutdown key in any UPS for more than 3 seconds and each one will be shutdown supplying output voltage through the bypass Turn On the outpu...

Страница 27: ...ot be fed Turn the manual bypass switch of the panel to Off UPS and put the mechanical lock To avoid wrong manoeuvring the mechanical lock has to be fit otherwise the equipment and loads are exposed t...

Страница 28: ...g Press the key for 1 sec as minimum to validate the modified option and change the settings Table 6 Functionality of the buttons or keypad of the control panel The UPS has a control panel with the fo...

Страница 29: ...TWIN Blue 72 Warning On maintain Bypass UPS only 8 20 kVA TWIN 3 Blue Code Condition Description Color LCD 81 Fault Heatsink over temperature Red 82 Alarm Ambient over temperature UPS only 4 10 kVA TW...

Страница 30: ...ad level connected to the UPS UPS power supply information three phase input UPS output information Equipment Battery information Fig 18 Main screen of the equipment with three phase input All the scr...

Страница 31: ...supply fails due to fault or wrong the equipment will transfer to Battery mode to feed the load s properly Fig 24 Frequency converter mode screen This function can be activated through the settings of...

Страница 32: ...ucture of the main menu includes six submenus UPS status Event log Measurement Control Identification Setting With password only and by the S T S 6 3 2 UPS status submenu When pressing the key for les...

Страница 33: ...ucture of UPS status menu Structure of main menu Press 1 sec Fig 31 UPS status screen Press 1 sec Press o 1 sec Structure of Data logger submenu Structure of main menu Press 1 sec Fig 32 Event logger...

Страница 34: ...rd only Fig 34 Control submenu screens 6 3 5 Control submenu When pressing the key the key for less than 1 sec from this Control submenu it is accessed to the control structure see figure 34 Shutdown...

Страница 35: ...ndard configuration from factory 6 4 1 Operating on ECO mode 6 4 1 1 Short description of the ECO mode ECO mode function allows supplying the load s from mains directly through the internal filters on...

Страница 36: ...en used for long time In hot areas battery has to be charged every 2 months The charging time has to be 12 hours as minimum Under normal conditions the battery lifetime is from 3 to 5 years 25 C In ca...

Страница 37: ...the UPS cooling and the ambient temperature of the room NTC abnormal UPS internal fault Consult with the S T S Communication cable male disconnected Para cable Male Loss Alarm code E3 Parallel bus ca...

Страница 38: ...oltage Inv Under Voltage Alarm code 33 UPS internal fault Consult with the S T S Inverter Softstart Failed Inv Softstart Fail Alarm code E34 UPS internal fault Consult with the S T S Negative Power Fa...

Страница 39: ...7 3 1 Covered product UPS SLC TWIN PRO series 7 3 2 Warranty terms This product is guaranteed against any parts and or labour defect for 12 months period from its commissioning by our company staff o...

Страница 40: ...age THD with non linear load 5 Output voltage recovering time 100 ms IEC 62040 3 70 ms IEC 62040 3 60 ms IEC 62040 3 Transient response of the output voltage with load fluctuation of 0 100 0 9 7 7 Tra...

Страница 41: ...elation to the working height 8 2 Glossary AC It is nominated as alternating current abbreviation in Spanish CA and in English AC to the electrical current in which the magnitude and direction varies...

Страница 42: ...rcuit when it over comes the maximum set values On Line mode Regarding to an equipment it is on line when it is connected to the system and it is in operation and usually has its power supply turned o...

Страница 43: ...43 SALICRU...

Страница 44: ...NCIA VALLADOLID ZARAGOZA BRANCHES AND SERVICES AND TECHNICAL SUPPORT S T S CHINA FRANCIA HUNGR A MARRUECOS M XICO PORTUGAL REINO UNIDO SINGAPUR SUBSIDIARIES ALEMANIA ARABIA SAUD ARGELIA ARGENTINA B LG...

Отзывы: