SALICRU
Code
Condition
Description
Color LCD
04
Warning
Site wiring fault (UPS only 4.. 10 kVA
TWIN).
Blue
05
Warning
Neutral or GND loss (UPS only 8.. 20
kVA TWIN/3).
Blue
11
State
Battery disconnect (UPS only 4.. 10
kVA TWIN).
Blue
11
Warning
Battery disconnect (UPS only 8.. 20
kVA TWIN/3).
Blue
12
State
Battery low (UPS only 4.. 10 kVA
TWIN).
Blue
12
Warning
Battery low (UPS only 8.. 20 kVA
TWIN/3).
Blue
14
State
Over charge.
Blue
15
State
Charger fail (UPS only 4.. 10 kVA
TWIN).
Blue
15
Warning
Charger fail (UPS only 8.. 20 kVA
TWIN/3).
Blue
16
Warning
Battery over voltage (UPS only 4.. 10
kVA TWIN).
Blue
1B
State
Battery test fail.
Blue
1C
State
Battery test interrupt.
Blue
21
Fault
BUS over voltage.
Red
22
Fault
BUS under voltage.
Red
23
Fault
BUS unbalance (UPS only 8.. 20 kVA
TWIN/3).
Red
24
Fault
BUS short.
Red
25
Fault
BUS softstart fail.
Red
26
Fault
Error de una fase.
Red
27
Alarm
IP fuse open (UPS only 4.. 10 kVA
TWIN).
Blue
31
Fault
Output short circuit.
Red
32
Fault
Inv over voltage.
Red
33
Fault
Inv under voltage.
Red
34
Fault
Inv softstart fail
Red
41
Fault
Output overload.
Red
42
Fault
Inv overload fault.
Red
43
Fault
Bypass overload fault.
Red
51
State
UPS control power On.
Blue
52
State
UPS On from panel.
Blue
53
State
UPS On from COM.
Blue
54
State
UPS auto On
Blue
55
State
UPS Off from panel.
Blue
56
State
UPS Off from COM.
Blue
57
State
UPS auto Off
Blue
61
State
In line mode (UPS only 4.. 10 kVA
TWIN).
Blue
62
State
In battery mode.
Blue
63
State
In ECO mode.
Blue
65
State
In converter mode.
Blue
71
Alarm
EPO active (UPS only 4.. 10 kVA
TWIN).
Blue
71
Warning
EPO active (UPS only 8.. 20 kVA
TWIN/3).
Blue
72
Alarm
On maintain Bypass (UPS only 4.. 10
kVA TWIN).
Blue
72
Warning
On maintain Bypass (UPS only 8.. 20
kVA TWIN/3).
Blue
Code
Condition
Description
Color LCD
81
Fault
Heatsink over temperature.
Red
82
Alarm
Ambient over temperature. (UPS only
4.. 10 kVA TWIN).
Blue
83
Alarm
Ambient NTC abnormal (UPS only 4..
10 kVA TWIN).
Blue
84
Alarm
Fan failure (UPS only 4.. 10 kVA TWIN).
Blue
85
Alarm
Fan lock (UPS only 4.. 10 kVA TWIN).
Blue
85
Warning
Fan lock (UPS only 8.. 20 kVA TWIN/3).
Blue
91
Alarm
OP relay openo (UPS only 4.. 10 kVA
TWIN).
Blue
92
Alarm
Model pin error (UPS only 4.. 10 kVA
TWIN).
Blue
93
Fault
Back feed.
Red
94
Warning
Byp relay sticked.
Blue
A1
Alarm
Read EEPROM error (UPS only 4.. 10
kVA TWIN).
Blue
E1
Fault
Fault negativo de potencia.
Red
E2
Fault
Negative power fault.
Red
E3
Alarm
Para cable male loss (UPS only 4.. 10
kVA TWIN).
Blue
E3
Warning
Para cable male loss (UPS only 8.. 20
kVA TWIN/3).
Blue
E4
Alarm
Para cable female loss (UPS only 4.. 10
kVA TWIN).
Blue
E4
Warning
Para cable female loss (UPS only 8.. 20
kVA TWIN/3).
Blue
E5
Alarm
Para cable loss (UPS only 4.. 10 kVA
TWIN).
Blue
E5
Warning
Para cable loss (UPS only 8.. 20 kVA
TWIN/3).
Blue
E6
Alarm
Para bat differ (UPS only 4.. 10 kVA
TWIN).
Blue
E6
Warning
Para bat differ (UPS only 8.. 20 kVA
TWIN/3).
Blue
E7
Alarm
Para line differ (UPS only 4.. 10 kVA
TWIN).
Blue
E7
Warning
Para line differ (UPS only 8.. 20 kVA
TWIN/3).
Blue
E8
Alarm
Para byp differ (UPS only 4.. 10 kVA
TWIN).
Blue
E8
Warning
Para byp differ (UPS only 8.. 20 kVA
TWIN/3).
Blue
E9
Warning
Para work mode differ (UPS only 8.. 20
kVA TWIN/3).
Blue
EA
Alarm
Para rate power differ (UPS only 4.. 10
kVA TWIN).
Blue
EA
Warning
Para rate power differ (UPS only 8.. 20
kVA TWIN/3).
Blue
EB
Alarm
ECO in para (UPS only 4.. 10 kVA
TWIN).
Blue
EB
Warning
ECO in para (UPS only 8.. 20 kVA
TWIN/3).
Blue
ED
Fault
Can commu fail
Red
EE
Alarm
Para number over (UPS only 4.. 10 kVA
TWIN).
Blue
Tabla 9.
UPS status and color LCD display, as condition.