DLY (DELUXE) SERIES HYDRONIC CASSETTE
.
9
SPECIFICATIONS – 2 PIPE SYSTEM
(4-WAY DISCHARGE SINGLE FAN CASSETTE)
Cooling: Entering air temperature: Dry bulb 27ºC, Wet bulb 19ºC;
Inlet water temp. 7ºC; Outlet water temp. 12ºC;
Heating: Entering air temperature: 20ºC;
Inlet water temp. 50ºC; Same water flow rate as for the cooling;
The customized power of electric heater is available.
The electric heater can be set as auxiliary heater booster or as primary heater, see control specifications.
SFP-170KM4-V/DLY
SFP-204KM4-V/DLY
SFP-238KM4-V/DLY
SFP-289KM4-V/DLY
Total capacity
(H/M/L)
kW
9.5/7.2/5.6
11.0/8.7/6.2
13.0/10.1/7.7
15.3/11.7/9.3
Sensible capacity
(H/M/L)
kW
8.3/6.3/4.9
9.7/7.6/5.4
10.5/8.2/6.2
11.5/8.4/6.4
Water flow rate
L/h
1,580
1,650
1,850
2,640
Pressure drop
kPa
15.5
17
20
36
Hot Water Heating
Capacity
(H/M/L)
kW
14.0/10.7/8.2
15.0/11.7/8.5
16.5/12.8/9.7
23.0/19.1/15.8
Evaparator Coil
Water content
L
2.53
2.53
2.53
2.98
Type
Size (Dia.)
mm
476
476
476
530
No. of fan
1
1
1
1
Power supply
V/Ph/Hz
Power input
W
170
175
234
330
Running current
A
0.78
0.80
1.07
1.43
m
3
/h
1700/1300/1000
2040/1600/1150
2380/1850/1400
2890/2100/1600
dB(A)
52/44/36
53/45/37
55/46/39
57/52/48
kW
3.0
3.0
3.0
3.0
A
13.6
13.6
13.6
13.6
mm
950x950x290
mm
1140x1140x30
kg
52
Method
In
mm(in)
Out
mm(in)
Socket (Threaded Female)
19.05(3/4")
19.05(3/4")
Water Connection
220~240 / 1 / 50 (60)
Chilled Water Cooling
Air Flow (H/M/L)
Electric Power
Panel Dimensions
Operation Control
Fan Blower
Model
Centrifugal type fan blower
Wireless remote controller and/or Wired wall pad
811x811x290
37
980x980x30
Electric Heater (optional)
Sound Pressure (1m,H/M/L)
Net Weight
Unit Dimensions (LxWxH)