DLY (DELUXE) SERIES HYDRONIC CASSETTE
.
13
SPECIFICATIONS – 4 PIPE SYSTEM
(6-WAY DISCHARGE TWIN FAN)
Cooling: Entering air temperature: Dry bulb 27ºC, Wet bulb 19ºC;
Inlet water temp. 7ºC; Outlet water temp. 12ºC;
Heating: Entering air temperature: 20ºC;
Inlet water temp. 70ºC; Outlet water temp. 60ºC;
SFP-85KM6-P/DLY
SFP-102KM6-P/DLY
SFP-136KM6-P/DLY
SFP-170KM6-P/DLY
Total capacity
(H/M/L)
kW
5.0/4.3/3.6
6.0/5.3/4.6
6.5/5.8/5.3
7.5/6.4/5.9
Sensible capacity
(H/M/L)
kW
3.7/3.2/2.9
4.4/3.9/3.3
5.0/4.5/3.8
6.0/5.2/4.8
Water flow rate
L/h
870
1,010
1,080
1,210
Pressure drop
kPa
18.5
19
22
26
Capacity
(H/M/L)
kW
9.5/8.0/7.0
10.5/9.0/7.4
12.0/10.0/8.2
13.0/10.5/9.3
Water flow rate
L/h
820
920
1,000
1,090
Pressure drop
kPa
16
20
23
26
Chilled water content
L
1.76
1.76
1.76
1.76
Hot water content
L
0.88
0.88
0.88
0.88
Type
Size (Dia.)
mm
315
315
315
315
No. of fan
2
2
2
2
Power supply
V/Ph/Hz
Power input
W
105
110
118
195
Running current
A
0.48
0.50
0.54
0.89
m
3
/h
850/700/550
1020/870/720
1360/1120/900
1700/1350/1100
dB(A)
45/41/39
49/45/40
54/50/45
59/56/51
mm
mm
kg
Method
In
mm(in)
Out
mm(in)
19.05(3/4")
19.05(3/4")
Wireless remote controller and/or Wired wall pad
1133x575x290
1240x680x30
Socket (Threaded Female)
Water Connection
Net Weight
Panel Dimensions
42
Hot Water Heating
Evaparator Coil
Air Flow (H/M/L)
Chilled Water Cooling
Model
Fan Blower
Electric Power
220~240 / 1 / 50 (60)
Unit Dimensions (LxWxH)
Centrifugal type fan blower
Sound Pressure (1m,H/M/L)
Operation Control
SAKURA - Total Air Conditioning Solution