![Sakura SFP-KM-DLY Series Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/sakura/sfp-km-dly-series/sfp-km-dly-series_installation-manual_3627882012.webp)
DLY (DELUXE) SERIES HYDRONIC CASSETTE
.
12
SPECIFICATIONS – 4 PIPE SYSTEM
(4-WAY DISCHARGE SINGLE FAN)
Cooling: Entering air temperature: Dry bulb 27ºC, Wet bulb 19ºC;
Inlet water temp. 7ºC; Outlet water temp. 12ºC;
Heating: Entering air temperature: 20ºC;
Inlet water temp. 70ºC; Outlet water temp. 60ºC;
SFP-170KM4-P/DLY
SFP-204KM4-P/DLY
SFP-238KM4-P/DLY
SFP-289KM4-P/DLY
Total capacity
(H/M/L)
kW
8.1/6.2/4.7
8.6/6.7/4.9
9.1/7.0/5.3
10.3/7.5/5.7
Sensible capacity
(H/M/L)
kW
7.0/5.3/4.1
7.5/5.9/4.2
8.1/6.2/4.7
8.5/6.2/4.7
Water flow rate
L/h
1,350
1,380
1,490
1,800
Pressure drop
kPa
26
26
31
40
Capacity
(H/M/L)
kW
9.6/7.3/5.6
10.6/8.5/6.2
11.2/8.7/6.6
13.7/10.3/7.9
Water flow rate
L/h
810
1,000
1,100
1,185
Pressure drop
kPa
14
20
22
28
Chilled water content
L
1.77
1.77
1.77
2.09
Hot water content
L
0.76
0.76
0.76
0.89
Type
Size (Dia.)
mm
476
476
476
530
No. of fan
1
1
1
1
Power supply
V/Ph/Hz
Power input
W
170
175
234
330
Running current
A
0.78
0.80
1.07
1.43
m
3
/h
1700/1300/1000
2040/1600/1150
2380/1850/1400
2890/2100/1600
dB(A)
52/44/36
53/45/37
55/46/39
57/52/48
mm
950x950x290
mm
1140x1140x30
kg
52
Method
In
mm(in)
Out
mm(in)
Hot Water Heating
Evaparator Coil
Water Connection
Air Flow (H/M/L)
Sound Pressure (1m,H/M/L)
Unit Dimensions (LxWxH)
Electric Power
811x811x290
980x980x30
Net Weight
Panel Dimensions
37
Socket (Threaded Female)
19.05(3/4")
Model
Chilled Water Cooling
Operation Control
Fan Blower
Centrifugal type fan blower
220~240 / 1 / 50 (60)
Wireless remote controller and/or Wired wall pad
19.05(3/4")
SAKURA - Total Air Conditioning Solution