DLY (DELUXE) SERIES HYDRONIC CASSETTE
.
15
5.
The installation location must have sufficient strength to carry the weight of the unit. The inlet grille and outlet
louvers are not obstructed and the treated air is able to blow all over the room.
6.
Check that it is possible to remove panels from ceiling in the selected position, to allow enough clearance for
maintenance and servicing operations.
7.
Check the distance between the upper slab and false ceiling to ensure the unit will suit the distance. (Fig.7)
8.
Ensure there is sufficient space around the unit to service it. (Fig.8)
Fig.7
Fig.8
5) INSTALLATION OF THE UNIT
1.
Mark position of suspension rods, water pipes and condensate drain hose, power supply cables, etc.
Supporting rods can be fixed, depending on the type of ceiling, as shown in Fig.9
2.
Fit mounting brackets of the unit to the threaded rods (Fig.10).
Do not tighten nuts and counter nuts; this operation has to be done only after final leveling of the unit, when all
the connections have been completed.
Fig.9 Fig.10
3.
Ensure the unit is horizontally level, otherwise condensate water can not drain.
4.
The casing is fixed to the slab with 4 drop rods. The rods should have two nuts and washers to lock the unit in
position. The mounting brackets will then hook over the washers.
5.
When lifting the unit body into position, take care by its four corners. Do not lift unit by the condensate drain
pipe or by the coil connections.
6.
Incline unit body and insert it into the false ceiling. Insert the rods into the bracket slot.
SAKURA - Total Air Conditioning Solution