11.
BUZZER
If a command is received by the air conditioner, the master unit will respond with 2 beeps for each setting, and
the slave unit will respond with 1 beep.
12.
AUTO RESTART
The system uses non-volatile memory to save the present operation parameters when system is turned off or
in case of system failure or cessation of power supply. Operation parameters when using handset are mode,
set temperature, swing, and the fan speed. When using wall pad parameters are mode, set temperature,
swing, and the fan speed When power supply resumes or the system is switched on again, the same
operations as previously set will function.
13.
WATER PUMP
Water pump turns on if thermostat cut in during cooling or dehumidification cooling cycle. It will remain on for
at least 5 minutes after thermostat cut out. During mode change from cooling to non cooling mode, water
pump will on for minimum 5 minutes.
14.
FLOAT SWITCH
This normally close switch is used to detect faults in water pump system. Switch open confirmation delay is
5sec while switch close confirmation is 60sec. Once switch is confirmed open, unload the thermostat, force
water pump to turn on for 5 minutes. Should water level switch be opened >= 2 times within 30 minutes,
thermostat is not allowed to cut in anymore. Turn off the unit to reset the fault provided that the switch has
returned to close position.
15.
OPERATION OF MANUAL RESET BUTTON ON UNIT PANEL
i. This is a tact switch to select Cool
ĺ
Heat
ĺ
Off operation mode.
ii. In cool mode, the set temperature of the system is 24ºC with auto fan speed and swing. There are
no timer and sleep modes.
iii. In heat mode, the set temperature of the system is 24ºC with auto fan speed and swing. There are
no timer and sleep modes.
iv. Master unit that does not use LCD wall pad will globally broadcast.
v. Master unit that does not use LCD wall pad will globally broadcast.
Note: When button pressing is effective, master unit buzzer will beep twice and slave unit beeps
once.
SAKURA - Total Air Conditioning Solution