DLY (DELUXE) SERIES HYDRONIC CASSETTE
.
10
SPECIFICATIONS – 2 PIPE SYSTEM
(6-WAY DISCHARGE TWIN FAN CASSETTE)
Cooling: Entering air temperature: Dry bulb 27ºC, Wet bulb 19ºC;
Inlet water temp. 7ºC; Outlet water temp. 12ºC;
Heating: Entering air temperature: 20ºC;
Inlet water temp. 50ºC; Same water flow rate as for the cooling;
The customized power of electric heater is available.
The electric heater can be set as auxiliary heater booster or as primary heater, see control specifications.
SFP-85KM6-V/DLY
SFP-102KM6-V/DLY
SFP-136KM6-V/DLY
SFP-170KM6-V/DLY
Total capacity
(H/M/L)
kW
6.0/5.1/4.2
7.0/6.0/5.35
8.0/6.9/6.1
9.0/7.65/6.9
Sensible capacity
(H/M/L)
kW
4.1/3.5/2.9
5.0/4.3/3.8
6.0/5.4/4.5
7.0/6.25/5.5
Water flow rate
L/h
990
1,130
1,290
1,440
Pressure drop
kPa
8
10
13
16
Hot Water Heating
Capacity
(H/M/L)
kW
8.6/7.1/6.3
10.2/8.6/7.4
11.0/9.7/8.0
12.3/10.5/9.2
Evaparator Coil
Water content
L
2.64
2.64
2.64
2.64
Type
Size (Dia.)
mm
315
315
315
315
No. of fan
2
2
2
2
Power supply
V/Ph/Hz
Power input
W
105
110
118
195
Running current
A
0.48
0.50
0.54
0.89
m
3
/h
850/700/550
1020/870/720
1360/1120/900
1700/1350/1100
dB(A)
45/41/39
49/45/40
54/50/45
59/56/51
kW
3.0
3.0
3.0
3.0
A
13.6
13.6
13.6
13.6
mm
mm
kg
Method
In
mm(in)
Out
mm(in)
220~240 / 1 / 50 (60)
Water Connection
Electric Power
Electric Heater (optional)
Air Flow (H/M/L)
Sound Pressure (1m,H/M/L)
1133x575x290
Panel Dimensions
Net Weight
Unit Dimensions (LxWxH)
Centrifugal type fan blower
Fan Blower
Chilled Water Cooling
Model
Operation Control
19.05(3/4")
Wireless remote controller and/or Wired wall pad
Socket (Threaded Female)
19.05(3/4")
42
1240x680x30
SAKURA - Total Air Conditioning Solution