DLY (DELUXE) SERIES HYDRONIC CASSETTE
.
52
5. SPECIFICATIONS OF THE CONTROL VALVE.
(I) THE ELECTRO THERMAL ACTUATOR (MODEL: T41)
The electro-thermal actuator is designed to control the open/close of the pipe of chiller or hot water through the
electro-thermal sensor inside the actuator. The valve is normally closed.
The electro-thermal actuator can be connected with the valve body quickly by using button connecting way.
Actuator Parameters
Material
Fireproof ABS engineering plastic
Housing
Color White
Control Element
Electro-thermal wax sensor
Connector M30×1.5
Working Ambient Temperature
烋
40
ć
First Fully Open Time
烋
6min
炷
25
ć
炸
Working Force
80N
Full Stroke
4.5mm
Protection Class
IP40
Power Consumption
1.1VA
Max.Impact Current
0.7A
Lead Wire
1m Length (2-core)
Net Weight
94g
Dimensions (mm)
Separate Gasket Dimensions
“MAX 2” means the max upward moving height
when component inside the electro-thermal actuator
is overloaded (2mm).
“Xmm” means the height from the top of the valve
stem to the top of the connector. Standard height
is 16mm.