SPECIFICATIONS – 4 PIPE SYSTEM
(4-WAY DISCHARGE SINGLE FAN)
Cooling: Entering air temperature: Dry bulb 27ºC, Wet bulb 19ºC;
Inlet water temp. 7ºC; Outlet water temp. 12ºC;
Heating: Entering air temperature: 20ºC;
Inlet water temp. 70ºC; Outlet water temp. 60ºC;
SFP-68KM4-P/DLY
SFP-80KM4-P/DLY
SFP-85KM4-P/DLY
SFP-102KM4-P/DLY
SFP-136KM4-P/DLY
Total capacity
(H/M/L)
kW
3.0/2.6/2.35
3.2/2.8/2.4
4.1/3.4/2.6
4.6/3.5/2.7
5.3/3.9/3.0
Sensible capacity
(H/M/L)
kW
2.4/2.2/1.7
2.6/2.3/1.75
3.1/2.6/1.9
3.6/2.7/2.1
4.3/3.2/2.3
Water flow rate
L/h
490
530
690
770
950
Pressure drop
kPa
10.5
11
10
11
14
Capacity
(H/M/L)
kW
6.1/4.7/3.6
6.3/5.0/3.7
7.6/6.0/4.6
8.0/6.1/4.7
8.6/6.4/4.9
Water flow rate
L/h
530
550
660
690
740
Pressure drop
kPa
4.5
5
9
10
11
Chilled water content
L
0.93
0.93
1.23
1.23
1.23
Hot water content
L
0.47
0.47
0.61
0.61
0.61
Type
Size (Dia.)
mm
315
315
380
380
380
No. of fan
1
1
1
1
1
Power supply
V/Ph/Hz
Power input
W
58
64
71
84
127
Running current
A
0.27
0.29
0.33
0.38
0.58
m
3
/h
680/520/400
800/630/470
850/700/530
1020/770/600
1360/1010/780
dB(A)
39/33/29
43/37/31
39/32/29
42/36/33
50/40/33
mm
mm
kg
Method
In
mm(in)
Out
mm(in)
19.05(3/4")
Hot Water Heating
Evaparator Coil
Water Connection
220~240 / 1 / 50 (60)
Air Flow (H/M/L)
Sound Pressure (1m,H/M/L)
Unit Dimensions (LxWxH)
Wireless remote controller and/or Wired wall pad
Electric Power
581x581x290
701x701x290
Net Weight
830x830x30
Panel Dimensions
680x680x30
25
Socket (Threaded Female)
29.5
19.05(3/4")
Model
Chilled Water Cooling
Operation Control
Fan Blower
Centrifugal type fan blower
SAKURA - Total Air Conditioning Solution