O p e r a t i o n s a n d I n s t r u c t i o n M a n u a l
13
S A G E M E T E R I N G , I N C .
REV. 03-SIE/SRE
COMPRESSION FITTING
A bored through tube fitting, properly sized to ac -
com modate an insertion probe’s particular OD, can
be provided by the user or purchased as an option
from Sage Metering (see page 34). Prior to installa-
tion, a clearance hole to accommodate the insertion
probe assembly must be drilled in the pipe/duct. A
fitting (1/2" FNPT) is then welded in place or thread-
ed into the half-threadolet which has been welded to
the pipe/duct. The probe insertion depth is adjustable
to permit sensor to be located at center, to optimize
measurement accuracy. (Refer to PROBE INSERTION
GUIDELINE DRAWING and CHART, pages 14 &15.)
Insert the probe shaft tubing into the
compression fitting to the position indicated
in the Probe Insertion guidelines.
While holding the fitting body steady,
tighten the nut one and one-quarter
turns to the 9 o’clock position.
INSTALLATION INSTRUCTIONS
1. Insert tubing into the tube fitting.
2. Make sure that the tubing is positioned properly
per the PROBE INSERTION GUIDELINE DRAW-
ING AND CHART, pages 14 &15.
3.
Due to the variations of tubing diameters, a
common starting point is desirable. Therefore,
tighten the nut until the tubing will not turn
by hand or move axially in the fitting.
4. Scribe the nut at the 6 o’clock position.
5. While holding fitting body steady, tighten the nut
1
1
⁄
4
turns to the 9 o’clock position.
Содержание SIE Series
Страница 2: ......
Страница 6: ......
Страница 7: ...Section GETTING STARTED A ...
Страница 8: ......
Страница 23: ...Section STYLES AND FEATURES B ...
Страница 24: ......
Страница 28: ......
Страница 29: ...Section DRAWINGS C ...
Страница 30: ......
Страница 39: ...Section USER INTERFACE D ...
Страница 40: ......
Страница 58: ......
Страница 59: ...Section DIAGNOSTICS E ...
Страница 60: ......
Страница 63: ...Section WARRANTIES AND SERVICE WORK F ...
Страница 64: ......
Страница 69: ...G Section APPENDIX G ...
Страница 70: ......