30
SL6+ v.3.30 EN
Configuration
OTHER CODES
CODE DATA COMMENTS
Receipt to alarm receiver
*84*
- # Select which message(s) to send to the alarm receiver
at an alarm call.
0 = None (default)
1 = Start of alarm
2 = Start+end of alarm
Break on new alarm
*86*
- # Disconnects a call longer than 60 sec. at new
activation of the alarm button and calls the next
emergency call number.
0 = Off
1 = On (default)
Alarm button delay time
*87*
- - # Delay time from pressing the alarm button until
activating the alarm.
00-25 seconds. Default = 05
Outputs
(Relay)
*88*
- - # The first number selects the relay output, i.e. Relay 1
or Relay 2.
The second number selects the function.
For SW 4.00 or later, the following parameters are
used:
0 = Alarm status outputs (default relay 1)
1 = Battery failure (default relay 2)
2 = Pictogram
(Relay 1: yellow, relay 2: green)
3 = Activate with DTMF 8/9
(relay 1 - DTMF 8, relay 2 - DTMF 9)
4 = Manual reset
5 = Emergency call failure
6 = System failure
7 = Emergency bell
Example
:
*88*11# - Relay 1, battery failure
*88*26# - Relay 2, system failure
For more information, please refer to "Relay func-
tions" (page 32)
For SW previous to 4.00, the following
parameters are used:
0 = Standard (default)
1 = EN81-28 Pictograms
2 = DTMF-controlled
3 = Manual - ECF (Emergency Call Fail)
For more information about the
parameters in the older versions,
please contact the support team.
Bus unit
*89*
- - #
Selected alarm input type for the bus unit
(N/O or N/C).
First number selects the bus unit (1-6).
Second unit selects N/O (0) or N/C (1).
Example:
*89*21# sets bus unit 2 as N/C