Speed min. voltage for winter auto fan
Speed max. voltage for winter auto fan
Speed min. voltage for summer auto fan
Speed max. voltage for summer auto fan
Cooling proportional band
Heating proportional band
General reset and restore of default values
Confirmation with O/I and Fan buttons
THERMOSTAT PARAMETERS –
Only for
T–MB
and
T–MB ± 3°C
versions
THERMOSTAT PARAMETERS –
Only for
T–MB ± 3°C
version
OFS
I-rL
Thermostat NTC probe offset variation
Relay hysteresis
± 3°C
0°C
dS
Set variation range with T–MB
± 9°C
± 3°C
0,5 ÷ 2,0°C
0,7°C
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
PARAMETERS of the T2 probe, CHANGE-OVER
T2-1
T2-2
Status changeover from ventilation to cooling
Status changeover from ventilation to heating
15 ÷ 24°C
<=20°C
30 ÷ 36°C
>=32°C
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
PARAMETERS of the T3 probe, TME minimum probe
T3-1
T3-2
Fan ON in heating mode (T3 probe)
Fan ON in cooling mode (T3 probe)
30 ÷ 40°C
>=34°C
10 ÷ 25°C
<=22°C
I-T3
T3 probe hysteresis
2 ÷ 8°C
5°C
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
OTHER FUNCTIONS
rE-t
F
UNCTION
D
ESCRIPTION
O
PERATION
PARAMETERS of the Stratification Cycle
t1SE
t1SI
Decompensation air probe T1 in cooling mode
Decompensation air probe T1 in heating mode
0,5 ÷ 2,0°C
0,7°C
0,5 ÷ 2,0°C
1,2°C
Ft1
Fan OFF time
10 - 20 min.
15 min.
Ft2E
Ft2I
Stratification time in cooling mode
30 - 180 sec.
120 sec.
Stratification time in heating mode
30 - 180 sec.
150 sec.
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
THERMOSTAT PARAMETERS –
Only for
T–MB–ECM
version
SHu3
SCu2
Speed max. voltage
Speed medium voltage
6 ÷ 10 V
10 V
3 ÷ 8 V
5 V
Slu1
Speed min. voltage
1 ÷ 6 V
1 V
LLSI
1 ÷ 6 V
1 V
HLSI
5 ÷ 10 V
10 V
LLSE
1 ÷ 6 V
1 V
HLSE
5 ÷ 10 V
10 V
PFC
2,0 ÷ 6,0°C
3,5°C
PFH
2,0 ÷ 6,0°C
3,5°C
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
Reset generale e ripristino valori di Default
Confermare con i tasti O/I e Fan
PARAMETRI TERMOSTATO –
Solo per versione
T–MB
e
T–MB ± 3°C
PARAMETRI TERMOSTATO –
Solo per versione
T–MB ± 3°C
OFS
I-rL
Variazione offset sonda NTC termostato
Isteresi dei relè
± 3°C
0°C
dS
Range di variazione del set con T–MB
± 9°C
± 3°C
0,5 ÷ 2,0°C
0,7°C
F
UNZIONE
D
ESCRIZIONE
R
ANGE
D
EFAULT
F
UNZIONE
D
ESCRIZIONE
R
ANGE
D
EFAULT
PARAMETRI Sonda T2, CHANGE-OVER
T2-1
T2-2
Cambio stato da ventilazione a raffrescamento
Cambio stato da ventilazione a riscaldamento
15 ÷ 24°C
<=20°C
30 ÷ 36°C
>=32°C
F
UNZIONE
D
ESCRIZIONE
R
ANGE
D
EFAULT
PARAMETRI Sonda T3, Sonda di minima TME
T3-1
T3-2
Ventilatore ON in riscaldamento (sonda T3)
Ventilatore ON in raffrescamento (sonda T3)
30 ÷ 40°C
>=34°C
10 ÷ 25°C
<=22°C
I-T3
Isteresi sonda T3
2 ÷ 8°C
5°C
F
UNZIONE
D
ESCRIZIONE
R
ANGE
D
EFAULT
ALTRE FUNZIONI
rE-t
F
UNZIONE
D
ESCRIZIONE
O
PERAZIONE
PARAMETRI Ciclo Antistratificazione
t1SE
t1SI
Scompensazione sonda aria T1 in raffrescamento
Scompensazione sonda aria T1 in riscaldamento
0,5 ÷ 2,0°C
0,7°C
0,5 ÷ 2,0°C
1,2°C
Ft1
Tempo di OFF del ventilatore
10 - 20 min.
15 min.
Ft2E
Ft2I
Tempo di Antistratificazione in raffrescamento
30 - 180 sec.
120 sec.
Tempo di Antistratificazione in riscaldamento
30 - 180 sec.
150 sec.
F
UNZIONE
D
ESCRIZIONE
R
ANGE
D
EFAULT
PARAMETRI TERMOSTATO –
Solo per versione
T–MB–ECM
SHu3
SCu2
Tensione max. velocità
Tensione med. velocità
6 ÷ 10 V
10 V
3 ÷ 8 V
5 V
Slu1
Tensione min. velocità
1 ÷ 6 V
1 V
LLSI
Tensione min. velocità per fan auto inverno
1 ÷ 6 V
1 V
HLSI
Tensione max. velocità per fan auto inverno
5 ÷ 10 V
10 V
LLSE
Tensione min. velocità per fan auto estate
1 ÷ 6 V
1 V
HLSE
Tensione max. velocità per fan auto estate
5 ÷ 10 V
10 V
PFC
Banda proporzionale in raffrescamento
2,0 ÷ 6,0°C
3,5°C
PFH
Banda proporzionale in riscaldamento
2,0 ÷ 6,0°C
3,5°C
F
UNZIONE
D
ESCRIZIONE
R
ANGE
D
EFAULT
> 3 sec.
> 3 sec.
FUNZIONI PER IL FACTORY
FEATURES FOR FACTORY
Questo menù consente di modificare i parametri
di funzionamento del termostato, del motore elettronico,
della ve/- 3 e di altri vari parametri (ciclo pompa, RESET).
Con il comando in
h/&&v
premere
i tasti
M
e
Fan
contemporaneamente per 3 secondi.
Scegliere il parametro da modificare
premendo i tasti “+” o “-” e confermare con il tasto “M”.
Una volta selezionato il parametro, il display visualizzerà il valore.
Il valore potrà essere modificato attraverso i tasti “+” o “-”.
Premendo una sola volta il tasto “M” si torna alla scelta di parametri;
per uscire dal menù premere il tasto “M” per più di 5 sec.
This menu allows modifying the operation
parameters of the thermostat, electronic motor, of the +/- 3 version
and many other parameters (pump cycle, RESET).
With the control set on
h/&&v
, press
the
M
and
Fan
buttons simultaneously for 3 seconds.
Select the desired parameter to be modified,
pressing button “+” or “-” and confirm using the “M” button.
Once the parameter is selected, the value will be displayed.
The value can be modified using button “+” or “-”.
Press the “M” button once to turn back to the parameter selection;
to exit the menu, press the “M” button for more than 5 seconds.