70
en
Temp. Sensor
L
R3
R2
R1
GND
S1
S2
S3
S4
S5
S6
S7
S8
CS1
0
V4
0/S
9
VBus
VBus GND
N
R4
R5
L'
VFD
PWM/0-10V
R5
RPD
IP20
Example of the electrical connection of a high-effi ciency pump
16.4 VBus
In this menu, sensors and relays can be allocated to the channels of a SDFK or SD6
remote display connected.
In order to do so, select the remote display connected in the new SDx… channel.
A sub-menu opens in which all adjustments required for the remote display can
be made.
Allocate the sensors and relays to the SDFK or SD6 respectively in the corre-
sponding sub-menus.
The following selections are available:
S1 … S9: Sensor inputs S1 … S9
CS10:
CS10 irradiation sensor (only if a corresponding sensor is connected)
VFD:
VFD temperature value (only if a corresponding sensor
is connected and registered)
RPD:
RPD temperature value (only if a corresponding sensor is connected
and registered)
R1 … R5: Relay outputs R1 … R5
HQM:
Heat quantity measurement (if more than one heat quantity measure-
ment has been activated, selecting HQM will refer to the fi rst heat quan-
tity measurement)
In- / outputs / VBus
Adjustment
channel
Description
Adjustment range / selection
Factory
setting
SDFK
SDFK selection
-
-
Channel 1 … 3 Sensor selection
None, S1 … S9, CS10, VFD, RPD -
Channel 4
Relay selection
None, R1 … R5
-
SD6
SD6 selection
-
-
Channel 1 … 5 Sensor / relay allocation
None, S1 … S9, CS10, VFD, RPD,
R1 … R5
-
Channel 6
Sensor / relay / HQM allocation
None, S1 … S9, CS10, VFD, RPD,
R1 … R5, HQM
-
SDx
Activation / Deactivation
Activated, Deactivated
Deactivated
Delete SDx
Delete remote display
Yes, No
No