10 Heating
In this menu, all adjustments for the heating part of the arrangement or for the
heating circuits respectively can be made.
Demands can be activated, heating circuits can be parameterised and optional func-
tions can be selected and adjusted.
10.1 Demands
Heating / Demands
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Dem. 1 (2)
Demand 1 (2)
Activated, Deactivated Deactivated
Relay
Relay option
Yes, No
-
Relay
Relay sub-menu
-
-
Output
Output selection
system dependent
system dependent
Boiler pr. min Option for boiler protection min
Yes, No
No
Tmin
Minimum boiler temperature
10 … 90 °C
55 °C
Boiler pr. max Option for boiler protection max
Yes, No
No
Tmax
Maximum boiler temperature
20 … 95 °C
90 °C
Sensor boiler Boiler sensor selection
system dependent
system dependent
0-10 V
0-10 V option
Yes, No
-
0-10 V
0-10 V sub-menu
-
-
Output
Output selection
-, A, B
-
Tset 1
Lower boiler temperature
10 … 90 °C
10 °C
Volt 1
Lower voltage
0.0 … 10.0 V
1.0 V
Tset 2
Upper boiler temperature
10 … 90 °C
80 °C
Volt 2
Upper voltage
0.0 … 10.0 V
8.0 V
Tmin
Minimum boiler temperature
1 … 90 °C
10 °C
Tmax
Maximum boiler temperature
1 … 90 °C
80 °C
∆
Tfl ow
Increase for the fl ow set temperature 0.0 … 45.0 K
5.0 K
Sen. Flow
Flow sensor option
Yes, No
No
Sensor
Flow sensor selection
system dependent
system dependent
Interval
Monitoring period
10 … 600 s
30 s
Correction
Correction of the voltage signal
0.1 … 1.0 V
0.1 V
Min. runtime Minimum runtime option
Yes, No
No
Min. runtime Minimum runtime
0 … 120 min
0 min
Funct.
Activation / Deactivation
Activated, Deactivated Deactivated