MCSE Series Operating Instructions 

ENGLISH

•  Maintain compressed air quality, i.e., filtration, pressure regulation, lubrication.

•  Avoid compressor oils that can cause valve seals to swell, soften, or otherwise 

deteriorate.

•  Conduct leakage tests of the load holding system, including the connecting lines, 

fittings, and actuator seals, on commissioning and periodically during use.

•  Operate within prescribed temperature limits.
•  Install the valve such that the normal stroke travel of the valve elements are 

perpendicular to the main direction of machine vibration and/or mechanical shock.

•  Avoid external magnetic fields.  

•  Do not plug the valve exhaust port.

•  Use only high-flow, non-clogging silencers, with similar or higher specifications as 

ROSS

®

 silencers.

2.1.3.  Diagnostic Coverage

A  diagnostic  coverage  of  99%  is  achievable  through  appropriate  integration  of  the  

MCSE

 Series valve into the safety control system. 

2.1.4.  Improper Use

 

  

WARNING

Risk of Injury!

Misuse may result in injury or damage.

 

f

The product must be used exclusively as intended.

The following applications are prohibited:

•  Use outdoors

•  Use in non-industrial applications/residential areas

•  Use outside of the product limits defined in the technical data

•  Unauthorized modifications

•  Use as a press safety valve to control a clutch or brake

•  Operation with a low demand rate (low demand mode) according to IEC 61508

•  Bypassing the safety function or diagnostics

•  Use in reverse operation (reversal of supply and exhaust air, reversal of output 

and supply)

 

ROSS CONTROLS is not liable for any damages resulting from improper use. 

The 

user alone bears the risks of improper use of the product.

2.2.  Responsibilities of the System Owner

•  Observe the information on assembly and operating conditions listed in the 

operating instructions or the data sheet.

•  Comply with the further requirements of ISO 13849 (e.g., CCF, DC, PLr, software) 

if you intend to use the product in higher categories (2, 3, or 4).

•  Make sure that the maximum number of switching cycles (B

10D

) within the service 

life T

m

 is not exceeded. If the expected number of switching cycles for a component 

exceeds the B

10D

 value during its period of use, suitable replacement intervals have 

to be specified.

•  Switch the valve at least once a month to ensure its proper operation.
•  Make sure that the fundamental and proven safety principles in accordance with 

ISO 13849 for implementation and operation of the component are complied with.

•  Make sure that the permissible positive and negative test pulses for feedback-

free operation of the pneumatic devices are observed (see chapter 11 “Technical 
Specifications“).

2.3.  Safety Instructions

•  When  implementing surge suppression measures, be sure to check whether or 

not this extends the valve shut off response time which could extend the machine 
stopping time.

•  In case of high levels of machine vibration, use appropriate vibration-reducing 

elements when installing the valve.

•  Supply the proper voltage as overvoltage situations can result in solenoid burnout.

•  Make  sure  that  the  silencer’s  flow  capacity  is  not  restricted  as  this  could  affect 

system performance. 

•  If required, replace the silencer exclusively with a corresponding ROSS model.

3.  Product Identification

Product label identification & product key identification example, see page 2. 

See back page for ROSS addresses.

4.  Prerequisites for Use of the Product

 

f

Make these operating instructions available to the engineer and assembly 

technician of the machine/system in which the product will be used.

 

f

Keep these operating instructions for the entire product life cycle.

4.1.  Qualified Personnel

Assembly, installation, commissioning, maintenance, and decommissioning should 

only be carried out by qualified personnel that have the required knowledge of and 

experience in dealing with electrical and pneumatic control technology.

5.  Package Contents

Items included:

•  MCSE 

Series double valve

•  Operating instructions

6.  Service and Maintenance

 

f

The  MCSE  valve  is  not  repairable.  Do  not  attempt  to  adjust  or  repair  the  valve. 

In case of technical problems or a required service, please contact your local 
ROSS representative. If used properly, the 

MCSE 

Series double valves will not 

require maintenance. Unless otherwise required, ROSS

®

 recommends performing 

a functional test at least once a month (see 8.1 Test Procedure). 

 

7.  Assembly and Installation

 

  

CAUTIONS

Risk of injury due to installation while pressurized or with live parts!

Installation while pressurized or with electrical power switched on can result in 

injuries due to sudden pressure build-up or electric shock.

 

f

De-energize and de-pressurize the relevant system parts before installing the valves.

 

f

 Secure the system to prevent it being switched back on again.

ATTENTION

Destruction of components!

Chemical substances can damage the surface, the markings and the seals of the device.

 

f

Install the valve such that it is protected against the effects of chemicals.

Damage to the device through storage at incorrect temperatures!

The storage temperature represents the permissible ambient temperature and de-

pends on the type of valve in question.

 

f

Observe the temperature information in chapter 11 “Technical Specifications.“

7.1.  Mechanical Installation

Prepare for assembly as follows:

1. Stop system operation and protect it against being switched on.

2. Return all suspended loads to a statically secure position or remove them from 

the system.
3. If required, exhaust stored compressed air from system parts in the immediate work area.

4. Make sure the relevant section of the system is not under pressure or voltage and 

protect it from being switched on.
5. Secure self-turning or other movable system parts before starting assembly.

6.  Let  the  MCSE  safety  valve  acclimatize  itself  for  several  hours  before  installation, 

otherwise water may condense in the housing.

Mount the Valve

To mount a single valve – See page 2.
To mount the valve as part of a maintenance unit – See page 2.

The valve must be mounted on both sides with one mounting element each on the 
mounting surface.

7.2.  Pneumatic Installation

Mount the pressure sensor or pressure gauge (optional)

A pressure gauge or electronic pressure sensor can be connected to the thread 
connection(see page 3) once the blanking plug has been removed.
Observe the mounting instructions enclosed with the components.

7.3.  Pneumatic and Electrical Connections

Pneumatic Connections

Requirement: The supply pressure must always be between 29 psig (2 bar) and up to 
145 psig (10 bar).
Note: The correct function of the MSCE safety valve is not guaranteed if the supply 
pressure is lower than 29 psig (2 bar) and up to 145 psig (10 bar).
1. Connect the pressure line for the supply pressure to connection 1 (1, IN).
2. Connect the operating line to connection 2 (2, OUT).

Electrical Connections

1. Connect the supply voltage to plug XPS, the signal output, and, if applicable, start 
signal X2.
The assignment of the XPS plug is the same for all versions.
The contacts on the XPS plug, M12 male have the following pin assignment:

Содержание MCSE Series

Страница 1: ...i disponibili per il download all indirizzo www rosscontrols com www rosscontrols com MCSE Series MCSE Series Safety Exhaust Dump Control Reliable Double Valves Serie MCSE Redundantes Sicherheitsventi...

Страница 2: ...PORT FITTING MCSE Valve 1 2 3 3 4 6 6 7 7 4 x 4 x 4 5 5 MCSE ROSS FRL s MD Series 3 4 6 7 REF NOTES Torque Max 54 FT LB 73NM NOTE PORT THREAD ARE AS PER STANDARDS FOR NPT THREAD ANSI ASME B1 20 1 FOR...

Страница 3: ...nciple Wiring for PM Control Figure 5 Principle Wiring for NCNO Control 1 2 3 4 S22 S12 5 1 2 3 4 24 V DC 0V GND X2 5 24 V DC 0 V GND S11 S21 n c 41 42 S22 S12 X2 t 0 V 24 V MCSE 0 1 1 2 3 4 5 6 7 Fig...

Страница 4: ...oid it 2 Notes on Safety The product has been manufactured according to the accepted rules of current technology There is risk of injury or damage if the following safety instructions and warnings giv...

Страница 5: ...tions available to the engineer and assembly technician of the machine system in which the product will be used f Keep these operating instructions for the entire product life cycle 4 1 Quali ed Perso...

Страница 6: ...he switch Safety input 2 S22 is connected with S21 via the switch Cross circuits on the safety inputs are monitored by the MCSE safety valve in this control Start pressurization takes place using the...

Страница 7: ...e second switch within synchronization time 6 the MCSE safety valve goes into the wait for start state at time 2 The MCSE safety valve remains in the non activated state MCSE 0 and the exhausts the op...

Страница 8: ...afety valve is ready IN 1 Green Off Safety input 1 P not actuated IN 1 Green Permanently illuminated Safety input 1 P actuated IN 1 Green Flashes quickly Time for synchronization exceeded IN 1 Green F...

Страница 9: ...g 3 1 Undefined level on input S22 Check the signals on plug X2D and the wiring 11 Technical Specifications Design Redundant 3 2 Normally Closed double valve internally monitored Actuation Electromagn...

Страница 10: ...e INNENGEWINDEANSCHLUSS MCSE Ventil 1 2 3 3 4 6 6 7 7 4 x 4 x 4 5 5 MCSE ROSS FRL s MD Serie 3 4 6 7 REF HINWEISE Anzugsdreh moment Max 54 FT LB 73NM HINWEIS ANSCHLUSSGEWINDE ENTSPRECHEN DEN NORMEN F...

Страница 11: ...Signalfolge bei Auftreten eines Fehlers Abbildung 9 Signalfolge f r PM Steuerung 1 2 3 4 5 24 V DC 24 V DC 0 V GND 0 V GND X2 41 42 1 2 3 4 n c 5 n c 1 2 3 4 5 24 V DC 0V GND n c S11 S21 1 2 3 4 5 1...

Страница 12: ...hrenabwehr Warndreieck Zeigt das Risiko f r t dliche oder schwere Verletzungen an Signalwort Zeigt die Schwere der Gefahr an Art oder Quelle der Gefahr Zeigt die Art oder Quelle der Gefahr Folgen Besc...

Страница 13: ...ellen Sie sicher dass die Durchflussleistung des D mpfers nicht eingeschr nkt ist da dies die Systemleistung beeinflussen kann Ersetzen Sie den Schalld mpfer falls erforderlich ausschlie lich durch ei...

Страница 14: ...V DC Versorgungsspannung ein Hinweis Die fehlerfreie Funktion des MSCE Sicherheitsventils ist nicht gew hrleistet wennderVersorgungsdrucknichtzwischen2bar 29psig undbiszu10bar 145psig liegt 1 Schlie...

Страница 15: ...d MCSE 1 Die OUT LED leuchtet auf und zeigt den aktivierten Zustand an Die Zeit f r das berwa chungssignal X2 liegt zwischen minimal 0 03 s und maximal 3 s Wird X2 innerhalb dieser berwachungszeit nic...

Страница 16: ...gen mit gr erem Volumen l nger als in Anlagen mit kleinerem Volumen 9 P ege und Wartung ACHTUNG Besch digungen des Produktes durch die Verwendung von L sungsmitteln und aggressiven Reinigungsmitteln D...

Страница 17: ...4 1 Zeit berwachung w hrend der Entl ftung Schalld mpfer verstopft Schalld mpfer austauschen 4 2 Zeit berwachung w hrend der Entl ftung Schalld mpfer verstopft Schalld mpfer austauschen 3 4 Undefinier...

Страница 18: ...erie MD CONECTOR DEL PUERTO HEMBRA V lvula MCSE 1 2 3 3 4 6 6 7 7 4 x 4 x 4 5 5 V lvula ROSS serie MD FRL 3 4 6 7 REF NOTAS Par M x 54 FT LB 73NM NOTA LA ROSCA DE PUERTO ES SEG N LOS EST NDARES PARA E...

Страница 19: ...7 Secuencia de se ales cuando se produce un fallo Figura 9 Secuencia de se ales para el control PM 1 2 3 4 5 24 V DC 24 V DC 0 V GND 0 V GND X2 41 42 1 2 3 4 n c 5 n c 1 2 3 4 5 24 V DC 0V GND n c S1...

Страница 20: ...n dise arse y construirse de forma que cumplan los requisitos de la categor a y el nivel de rendimiento NR del sistema de seguridad que resultan de la evaluaci n de riesgos de la m quina Con una corre...

Страница 21: ...to f Ponga estas instrucciones de servicio a disposici n del ingeniero y del t cnico de montaje de la m quina sistema en la que se va a utilizar el producto f Conserve estas instrucciones de servicio...

Страница 22: ...s entradas de seguridad 1 y 2 con la secuencia de se ales adecuada Si la secuencia de se ales no es correcta la v lvula de seguridad MCSE pasa al estado seguro El escape de la l nea de operaci n es el...

Страница 23: ...s LED IN 1 e IN 2 est n apagados en este estado y el bot n de arranque X2 debe volver a presionarse 8 1 6 Secuencia de se ales para el control NCNO Durante el control por NCNO de la v lvula de segurid...

Страница 24: ...ia qu mica del material de la v lvula frente a dichos productos Los disolventes y los detergentes agresivos destruir n la superficie el etiquetado y los sellos del producto f Aseg rese de que ning n d...

Страница 25: ...sustituir el silenciador 3 4 Nivel no definido en la entrada X2 Comprobar las se ales del enchufe XPS y el cableado 2 9 Nivel no definido en la entrada S12 Comprobar las se ales del enchufe X2D y el c...

Страница 26: ...ROSS POSE DU PORT FEMELLE MCSE Vanne 1 2 3 3 4 6 6 7 7 4 x 4 x 4 5 5 MCSE S rie MD de ROSS FRL 3 4 6 7 R F REMARQUES Couple Max 54 FT LB 73NM POUR FILETAGE NPT ANSI ASME B1 20 1 POUR FILETAGE G ISO 2...

Страница 27: ...de signaux si une d faillance survient Figure 9 S quence de signaux pour commande PM 1 2 3 4 5 24 V DC 24 V DC 0 V GND 0 V GND X2 41 42 1 2 3 4 n c 5 n c 1 2 3 4 5 24 V DC 0V GND n c S11 S21 1 2 3 4 5...

Страница 28: ...ctions comportant des exigences de manipulation qui s accompagnent de risques de blessures ou de dommages mat riels Les avertissements sont structur s comme suit TERME DE SIGNALISATION Type ou source...

Страница 29: ...onctionnement sans retour des appareils pneumatiques voir le chapitre 11 Caract ristiques techniques 2 3 Instructions de s curit Lors de la mise en uvre des mesures de suppression des surtensions veil...

Страница 30: ...t la mise en service l installation doit faire l objet d une inspection soigneuse par un professionnel qualifi et form Veillez ce que les caract ristiques techniques correspondent aux crit res d utili...

Страница 31: ...nal de d marrage X2 passe de 0 V 24 V c t positif l heure 3 puis repasse de 24 V 0 V c t n gatif l heure 4 la vanne de s curit MCSE passe l tat pressuris MCSE 1 l heure 4 La DEL OUT s allume et indiqu...

Страница 32: ...solvants et des agents nettoyants agressifs Le produit peut tre endommag s il est lav avec un solvant ou avec un agent nettoyant agressif La r sistance chimique du mat riau de la vanne ces produits n...

Страница 33: ...eau de l entr e X2 V rifiez les signaux de la prise XPS et le c blage 2 9 Niveau ind fini au niveau de l entr e S12 V rifiez les signaux de la prise X2D et le c blage 3 1 Niveau ind fini au niveau de...

Страница 34: ...D RACCORDO PORTA FEMMINA MCSE Valvola 1 2 3 3 4 6 6 7 7 4 x 4 x 4 5 5 MCSE Serie MD della ROSS FRL 3 4 6 7 RIF NOTE Coppia Max 54 FT LB 73NM NOTA LE FILETTATURE DELLE PORTE SONO COME DA STANDARD PER F...

Страница 35: ...Sequenza di segnali in presenza di un guasto Figura 9 Sequenza di segnali per controllo PM 1 2 3 4 5 24 V DC 24 V DC 0 V GND 0 V GND X2 41 42 1 2 3 4 n c 5 n c 1 2 3 4 5 24 V DC 0V GND n c S11 S21 1...

Страница 36: ...io Conseguenze f Misure per prevenire il pericolo Triangolo di avvertimento Indica un rischio di lesioni gravi o mortali Dicitura dell avvertimento Indica la gravit del pericolo Tipo o fonte del risch...

Страница 37: ...lla valvola Fornire la tensione corretta in quanto situazioni di sovratensione possono causare la bruciatura delle solenoidi Assicurarsi che la capacit di portata del silenziatore non sia limitata dat...

Страница 38: ...7 3 Collegamenti pneumatici e elettrici Collegamenti pneumatici Requisito La pressione di mandata deve sempre essere tra 29 psig 2 bar e 145 psig massimo 10 bar Nota Il funzionamento corretto della va...

Страница 39: ...ale X2 cambia da 0 V a 24 V fianco positivo al tempo 3 e ricambia da 24 V a 0 V fianco negativo al tempo 4 la valvola di sicurezza MCSE passa allo stato pressurizzato MCSE 1 al tempo 4 Il LED OUT si a...

Страница 40: ...E Danno al prodotto a causa dell uso di solventi e detergenti aggressivi Il prodotto pu danneggiarsi se viene lavato con un solvente o un detergente aggressivo Non si garantisce la resistenza chimica...

Страница 41: ...occato sostituire il silenziatore 3 4 Livello non definito su ingresso X2 Controllare i segnali sulla spina XPS e il cablaggio 2 9 Livello non definito su ingresso S12 Controllare i segnali sulla spin...

Страница 42: ...7 7 4 x 4 x 4 5 5 MCSE M R SS R 3 4 6 7 4 B M P ANSI ASME B1 20 1 ISO 228 1 M R SS 5 2 4 2 4 B 4 M 4X 4 M 23 1 5 0 91 0 06 137 5 39 M12 65 2 26 167 8 2 5 6 60 0 10 2x G1 58 2 28 28 5 1 12 53 2 09 5 30...

Страница 43: ...42 S21 S22 S11 S12 1 2 3 4 M n c P 5 n c 1 2 3 4 24 V DC 0V GND X2 5 24 V DC 0 V GND 1 2 3 4 5 n c DO P DO M 1 2 3 4 S22 S12 5 1 2 3 4 24 V DC 0V GND X2 5 24 V DC 0 V GND S11 S21 n c 41 42 S22 S12 X2...

Страница 44: ...07 A1 2011 Electromagnetic compatibil ity Generic standards Emission standard for industrial environments ENISO4414 2010 11 Pneumatic Fluid Power General Rulesand Safety Requirementsfor Pneumatic Syst...

Страница 45: ...ommon ause Failures F F R SS 2 1 3 99 MCSE 2 1 4 f IE 6150 R SS TR LS 2 2 IS 13 49 F D Lr 2 3 4 B10D Tm B10D IS 13 49 11 2 3 R SS 3 42 R SS 4 f f 4 1 5 M SE 6 f M SE R SS MCSE R SS 1 7 f f f f 11 7 1...

Страница 46: ...M SE D0 M M SE D0 2 24 M M 2 43 7 3 7 M SE DI E 60204 1 IE 60204 1 8 f f 10 8 1 MCSE M SE 1 2 24 7 3 29 2 145 10 MS E 29 2 145 10 1 1 1 I 2 2 2 T 1 S 2 S M12 S 2 2D 7 3 1 f SEL 24 EL DI E 60204 1 f EL...

Страница 47: ...S12 S11 6 M SE 2 M SE M SE 0 T 0 5 1 2 I 1 I 2 1 2 M SE M SE 0 M SE T I 1 I 2 1 2 2 0 24 3 24 0 4 M SE M SE 1 4 T 2 0 03 3 2 M SE M SE 0 S11 S12 S21 S22 4 M SE M SE 0 5 T 1 2 I 1 I 2 2 8 1 6 NCNO 7 3...

Страница 48: ...3 3 9 4 1 4 2 3 4 2 2 9 S12 3 1 S22 8 2 1 M SE 24 R I 1 I 2 T ERR R I 1 I 2 T ERR M SE I 1 1 I 1 1 I 1 I 1 S22 I 2 2 M I 2 2 M I 2 I 2 S12 ut M SE ut M SE ut M SE 2 ERR ERR ERR 8 2 2 M SE 50 42 50 50...

Страница 49: ...1 3 30 150 2 10 23 120 F 5 50 4 IS 573 3 7 24 SEL DI E 60950 EL E IE 60204 1 S12 S22 2 24 S11 21 20 10 1500 1 5 2500 2 5 40 2 0 IE 60529 E 60529 I 65 1 1x 5 M12 150 10 10 5 1 5 41 42 24 0 2 2006 42 E...

Страница 50: ...50 www rosscontrols com...

Страница 51: ...www rosscontrols com 51...

Страница 52: ...sales rosscanada com www rosscanada com 6077170 CANADA INC AN INDEPENDENT REPRESENTATIVE Brazil ROSS SOUTH AMERICA Ltda 55 11 4335 2200 vendas rosscontrols com www rosscontrols com br EUROPE Germany...

Отзывы: