6.1 Technical Data
Nominal voltage:
AC 230/400V 50Hz (+6% / -10%)
Control voltage:
AC 24V 50Hz,
disconnected galvanically from the mains
voltage
Ambient temperature
Operating device and
-20°C to +60°C max. 90%r.F.
IP protection type of the external operat-
ing device
IP40 for wall mounting / IP65 for front mount-
ing
Wire connection from the control to the
operating device
Li9YY6 not crossed with RJ 11 Telephone
plug,
10m cable enclosed
length max.: 50m (without TCONN6J000)
Conductor
NYM-J 3x2,5mm²
Maximum power of the alarm relay
AC 250V 10A for 1,5mm
2
core cross-section
The alarm relay energizes as soon as the Suprabox COMFORT (SBC) is live.
In case of an alarm or the interruption of the voltage supply the relay de-energizes.
6.2 Terminal configuration
The terminal configuration has to be performed exclusively according to the valid wiring.
The electric potentials must be observed when mounting and wiring. Incorrect wiring
may damage the electronic circuit or lead to wrong logically program routine.
If after reading the operating instructions and the circuit diagram there are still some
questions regarding installation, operation or maintenance please contact the Rosen-
berg Ventilatoren GmbH.