50
16 Initial Operation Report
Direction
Horizontal
Vertical
Ceiling assembly
Control tem-
perature
Fresh air temperature
Return air temperature
Room temperature
Fans
Maximum
value:_____________
Minimum
value:_______________
Imbalance:__________
Fresh air fan
Speed control,
checked
Air volume control,
checked
Pressure con-
trol, checked
Fixed val-
ue, checked
Follow up,
checked
Return Fan
Speed control,
checked
Air volume control,
checked
Pressure con-
trol, checked
Fixed val-
ue, checked
Follow up,
checked
Fans free-moving in disconnected status.
Operation manuals are available ________________________________________________
Sensor Overriding
Sensor type: _______________________________
Sensor Automatic operation
Sensor type: _______________________________
Filter flow direction considered
Limiting Value of the differential pressure control for monitoring WRG freeze, checked and set. Value _____________
Supply air duct sensor placed behind the coil if fresh air heating/cooling is used.
Direction of rotation of the bypass damper checked and set.
Direction of rotation of the outside air/return air damper checked and set (in case that accessories are connected)
Condensate drain correctly connected (trap, anti-freezing protection)
Warm water coil connected (flow, return flow correct, valve switching checked)
Anti-Freeze protection cor-
rectly connected and checked.
Anti-freeze thermostat(behind the heating coil)
Contact thermostat(at the
return flow, close to the coil)
Cold water cooling coil connected (flow, return flow correct, valve switching checked)
Electric heating connected
Overheat control and air volume control connected and checked
Electro-preheating connected
Overheat control and if necessary air volume control (not for integrated PTC) connected and checked
Direct evaporator/ refrigerator connected and checked
Size
800 m³/h
1100 m³/h
1500 m³/h
1900 m³/h
2000 m³/h
3500 m³/h
5000 m³/h