43
Service menu
(supply air limit)
(Minimum)
(Maximum)
16.0°C
38.0°C
Service menu
(Control type heating)
(Type)
(P-Band)
(Integration time)
PI-Control
40.0°C
100s
Service menu
(Control type cooling )
(Typ)
(P-Band)
(Integration time)
PI-Control
40.0°C
100s
Service menu
(break time)
(heating and cooling)
(cooling and heating)
2Min.
2Min.
Operation level
Nominal value Supply air fan
…%, Pa, m
3
/h
As required
Operation level
Nominal value return air fan
…%, Pa, m
3
/h
As required
Service menu
(operating mode of the fan)
Volume flow
Operation level
Automatic calculation of the fan nominal
value
No
Service menu
(Automatic mode dictated by)
Sensor 0-10V
Temperature
differ-
ence
free
Operation level
Selection time control and Week pro-
gram
No
Operation level
Selection night air
No
Service menu
(Temperature sensor room air)
free
Service menu
(Night air limit value Room temperature.)
24.0°C
Service menu
(Night air limit value Outdoor temperature.)
16.0°C