![Rosemount Oxymitter 5000 Скачать руководство пользователя страница 190](http://html1.mh-extra.com/html/rosemount/oxymitter-5000/oxymitter-5000_instruction-manual_1487464190.webp)
Hazardous Area Oxymitter 5000
D-12
Instruction Manual
IM-106-350C, Rev 2.2
July 2008
Differential Pressure
Transmitter to Measure
Flow
Situation
The liquid flow in a line is to be measured using the differential pressure
across an orifice plate in the line, and the flow measurement will be used in a
flow control loop. Based on the orifice specification sheet, the differential
pressure transmitter was calibrated for 0 to 20 in H
2
0 for a flow of 0 to 800
gal/min, and the transducer was not configured to take the square root of the
differential pressure.
Solution
Table D-6 lists the appropriate configuration settings, and Figure D-7
illustrates the correct function block configuration.
Table D-6. Analog Input
Function Block Configuration for
a Differential Pressure
Measurement
Figure D-7. Function Block
Diagram for a Differential
Pressure Transmitter Used in a
Flow Measurement
Parameter
Configured Values
L_TYPE
Indirect Square Root
XD_SCALE
0 to 20 in.
OUT_SCALE
0 to 800 gal/min
38740089
AI
Function
Block
PID
Function
Block
AO
Function
Block
OUT_D
OUT
Analog
Measurement
BKCAL_INBKCAL_OUT
IN
Содержание Oxymitter 5000
Страница 2: ......
Страница 6: ......
Страница 14: ...Hazardous Area Oxymitter 5000 iv Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 82: ...Hazardous Area Oxymitter 5000 7 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 130: ...Hazardous Area Oxymitter 5000 9 24 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 140: ...Hazardous Area Oxymitter 5000 11 6 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 172: ...Hazardous Area Oxymitter 5000 B 2 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 192: ...Hazardous Area Oxymitter 5000 D 14 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 210: ...Hazardous Area Oxymitter 5000 E 18 Instruction Manual IM 106 350C Rev 2 2 July 2008 ...
Страница 212: ...Instruction Manual IM 106 350C Rev 2 2 July 2008 Hazardous Area Oxymitter 5000 Index 2 ...