Reference Manual
00809-0100-4848, Rev AA
July 2009
3-7
Rosemount 848T Wireless
PHYSICAL
INSTALLATION
Remote Mount
The Rosemount 848T Wireless can only be installed in the Remote Mount
configuration where the sensor is mounted separate from the 848T housing,
then connected to the 848T using conduit or cable glands.
1. Install the sensor according to standard installation practices. Be sure
to use thread sealant on all connections.
2.
To reduce sensor wiring length, mount the Rosemount 848T Wireless
transmitter central to all of the measurements. When installing the
848T wireless, the conduit entries need to be facing downward. If
using the mounting bracket (Option Code B6), mount to a 2-in. pipe.
3. Run wiring (and conduit, if necessary) from the sensor to the 848T.
For an easier installation, use the outside conduit entries, as shown
below. Any unused conduit entries should be sealed with an
approved sealant using the included threaded conduit plug.
Conduit Entries
Conduit Plug
Conduit Entries