Reference Manual
00809-0100-4024, Rev BA
September 2005
Rosemount 5600 Series
4-6
Advanced Tank
Geometry Configuration
Advanced configuration is done through the following parameters:
Distance Offset (G)
The Distance Offset (G) is defined as the distance between the
upper reference point and the flange (the flange is referred to as
the Transmitter’s Reference Point). You can use the Distance
Offset to specify your own reference point at the top of the tank.
Set the Distance Offset to zero if you want the flange as upper
reference point. The Distance Offset is defined as positive if you
use an upper reference point above the Transmitter’s Reference
Point. The Distance Offset is used when the measured level by the
transmitter should correspond with the level value obtained by
hand-dipping.
Minimum Level Offset (C)
The Minimum Level Offset (C) defines a lower null zone which
extends the measurement range beyond the Zero Level Reference
Point down to the tank bottom. The Minimum Level Offset is
defined as the distance between the zero level (Tank Level
Reference Point) and the minimum accepted level and tank
bottom. Set the Minimum Level Offset to zero if you use the tank
bottom as zero level reference point. If the zero level is not defined
as the tank bottom and instead is an elevated point as the datum
plate, you need to define the Minimum Level Offset.
Note: The Minimum Level Offset can not be negative.
Calibration Distance
The Calibration Distance is by default set to zero. It is used to
adjust the transmitter so that measured levels match hand dipped
product levels. Normally a minor adjustment is necessary. There
may for example be a deviation between the actual tank height and
the value stored in the transmitter database.
Show Negative Values as
Zero
Set this parameter if you want levels below the reference point at
the bottom of the tank to be displayed as zero. This parameter can
be used if you have set a Minimum Level Offset distance in the
tank geometry configuration.
5600/SCREEN DUMP
S/1
1G
EOMETRYADVANCED.TIF
Distance Offset (G)
Hold Off
Distance (UNZ)
Minimum Level
Offset (C)
Tank Height (R)
Transmitter’s
Reference Point
Содержание 5600 Series
Страница 2: ......
Страница 4: ......
Страница 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Страница 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Страница 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Страница 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Страница 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Страница 130: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 6 20 F OUNDATION Fieldbus ...
Страница 144: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 7 14 2210 Display Unit ...
Страница 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Страница 185: ...Reference Manual 00809 0100 4024 Rev BA September 2005 B 11 Rosemount 5600 Series 5600APPROVAL03 EPS ...
Страница 186: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series B 12 5600APPROVAL04 EPS ...
Страница 196: ...Reference Manual 00809 0100 4025 Rev BA April 2002 Rosemount 5600 Series C 8 F OUNDATION Fieldbus ...
Страница 204: ...Reference Manual 00809 0100 4025 Rev BA September 2005 Rosemount 5600 Series E 4 F OUNDATION Fieldbus ...
Страница 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Страница 209: ......