Reference Manual
00809-0100-4024, Rev BA
September 2005
Rosemount 5600 Series
8-4
FIELDBUS
MAINTENANCE AND
TROUBLESHOOTING
Methods and Manual Operation
Each F
OUNDATION
fieldbus host or configuration tool has different ways of
displaying and performing operations. Some hosts will use Device
Descriptions (DD) and DD Methods to complete device configuration and will
display data consistently across platforms. The DD can be found on
www.rosemount.com. There is no requirement that a host or configuration tool
support these features.
The information in this section will describe how to use methods in a general
fashion. In addition, if your host or configuration tool does not support
methods this section will cover manually configuring the parameters involved
with each method operation. For more detailed information on the use of
methods, see your host or configuration tool manual.
Configure Transmitter
Refer to Section 6: FOUNDATION Fieldbus Configuration for further
information regarding the configuration of the Radar Transmitter.
Service Method
This method is for service purpose only. If your host does not support
methods ENV_DEVICE_MODE it needs to be manually configured.The
following options are available:
•
F
OUNDATION
™
fieldbus:
Set the device in normal fieldbus communication mode.
•
Sensor bus:
Set the device in sensor bus mode, which means that all
communication goes through the external sensor bus instead of the
fieldbus. This is used to connect PC configuration tools.
•
Restart transmitter:
Restarts the device, not the fieldbus card.
•
Set to factory default:
Sets all configured data to factory settings.
Calibration Distance
Configuration
See page 4-6 for further information.
Master Reset Method
(Resource Block)
To perform a master reset, run the Master Reset Method. If your system does
not support methods, manually configure the Resource Block parameters
listed below.
1. Set the RESTART = Run, Resource, Defaults, or Processor
•
Run = nominal state when not restarting (default)
•
Resource = not used by device
•
Defaults = sets parameters to FOUNDATION fieldbus default values
•
Processor = does a warm start of the fieldbus card and the transmitter
Write Protection
(Resource Block)
Inputs to the security and write lock functions include the hardware security
jumper, the hardware and software write lock bits of the FEATURE_SEL
parameter, the WRITE_LOCK parameter, and the DEFINE_WRITE_LOCK
parameter.
F
OUNDATION
Fieldbus
Содержание 5600 Series
Страница 2: ......
Страница 4: ......
Страница 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Страница 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Страница 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Страница 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Страница 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Страница 130: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 6 20 F OUNDATION Fieldbus ...
Страница 144: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 7 14 2210 Display Unit ...
Страница 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Страница 185: ...Reference Manual 00809 0100 4024 Rev BA September 2005 B 11 Rosemount 5600 Series 5600APPROVAL03 EPS ...
Страница 186: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series B 12 5600APPROVAL04 EPS ...
Страница 196: ...Reference Manual 00809 0100 4025 Rev BA April 2002 Rosemount 5600 Series C 8 F OUNDATION Fieldbus ...
Страница 204: ...Reference Manual 00809 0100 4025 Rev BA September 2005 Rosemount 5600 Series E 4 F OUNDATION Fieldbus ...
Страница 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Страница 209: ......