Reference Manual
00809-0100-4024, Rev BA
September 2005
Rosemount 5600 Series
D-2
F
OUNDATION
Fieldbus
PARAMETERS AND
DESCRIPTIONS
The table below lists all of the configurable parameters of the Resource Block,
including the descriptions and index numbers for each.
Parameter
Index
Number
Description
ACK_OPTION
38
Selection of whether alarms associated with the function block will be
automatically acknowledged.
ADVISE_ACTIVE
82
Enumerated list of advisory conditions within a device.
ADVISE_ALM
83
Alarm indicating advisory alarms. These conditions do not have a direct impact on the
process or device integrity.
ADVISE_ENABLE
80
Enabled ADVISE_ALM alarm conditions. Corresponds bit for bit to the ADVISE_ACTIVE.
A bit on means that the corresponding alarm condition is enabled and will be detected. A
bit off means the corresponding alarm condition is disabled and will not be detected.
ADVISE_MASK
81
Mask of ADVISE_ALM. Corresponds bit of bit to ADVISE_ACTIVE. A bit on means that
the condition is masked out from alarming.
ADVISE_PRI
79
Designates the alarming priority of the ADVISE_ALM
ALARM_SUM
37
The current alert status, unacknowledged states, unreported states, and disabled states
of the alarms associated with the function block.
ALERT_KEY
04
The identification number of the plant unit.
BLOCK_ALM
36
The block alarm is used for all configuration, hardware, connection failure or system
problems in the block. The cause of the alert is entered in the subcode field. The first alert
to become active will set the Active status in the Status parameter. As soon as the
Unreported status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active status, if the subcode has changed.
BLOCK_ERR
06
This parameter reflects the error status associated with the hardware or software
components associated with a block. It is a bit string, so that multiple errors may be
shown.
CLR_FSAFE
30
Writing a Clear to this parameter will clear the device FAIL_SAFE if the field condition has
cleared.
CONFIRM_TIME
33
The time the resource will wait for confirmation of receipt of a report before trying again.
Retry will not happen when CONFIRM_TIME=0.
CYCLE_SEL
20
Used to select the block execution method for this resource. The Rosemount 5600
supports the following:
Scheduled: Blocks are only executed based on the function block schedule.
Block Execution: A block may be executed by linking to another blocks completion.
CYCLE_TYPE
19
Identifies the block execution methods available for this resource.
DD_RESOURCE
09
String identifying the tag of the resource which contains the Device Description for
this resource.
DD_REV
13
Revision of the DD associated with the resource - used by an interface device to locate
the DD file for the resource.
DEFINE_WRITE_LOCK
60
Allows the operator to select how WRITE_LOCK behaves. The initial value is “lock
everything”. If the value is set to “lock only physical device” then the resource and
transducer blocks of the device will be locked but changes to function blocks will be
allowed.
DETAILED_STATUS
55
Indicates the state of the transmitter. See Resource Block detailed status codes.
DEV_REV
12
Manufacturer revision number associated with the resource - used by an interface device
to locate the DD file for the resource.
DEV_STRING
43
This is used to load new licensing into the device. The value can be written but will always
read back with a value of 0.
DEV_TYPE
11
Manufacturer’s model number associated with the resource - used by interface devices to
locate the DD file for the resource.
DIAG_OPTION
46
Indicates which diagnostics licensing options are enabled.
DISTRIBUTOR
42
Reserved for use as distributor ID. No Foundation enumerations defined at this time.
DOWNLOAD_MODE
67
Gives access to the boot block code for over-the-wire downloads.
0 = Uninitialized
1 = Run mode
2 = Download mode
Содержание 5600 Series
Страница 2: ......
Страница 4: ......
Страница 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Страница 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Страница 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Страница 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Страница 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Страница 130: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 6 20 F OUNDATION Fieldbus ...
Страница 144: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 7 14 2210 Display Unit ...
Страница 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Страница 185: ...Reference Manual 00809 0100 4024 Rev BA September 2005 B 11 Rosemount 5600 Series 5600APPROVAL03 EPS ...
Страница 186: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series B 12 5600APPROVAL04 EPS ...
Страница 196: ...Reference Manual 00809 0100 4025 Rev BA April 2002 Rosemount 5600 Series C 8 F OUNDATION Fieldbus ...
Страница 204: ...Reference Manual 00809 0100 4025 Rev BA September 2005 Rosemount 5600 Series E 4 F OUNDATION Fieldbus ...
Страница 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Страница 209: ......