Reference Manual
00809-0100-4024, Rev BA
September 2005
Rosemount 5600 Series
8-6
Block Instantiation
The Rosemount 5600 supports the use of Function Block Instantiation. When
a device supports block instantiation, the user can define the number of
blocks and block types to match specific application needs. The number of
blocks that can be instantiated is only limited by the amount of memory within
the device and the block types that are supported by the device. Instantiation
does not apply to standard device blocks like the Resource, Level Transducer,
and Register Transducer Block. Block instantiation is done by the host control
system or configuration tool, but not all hosts are required to implement this
functionality. Please refer to your specific host or configuration tool manual for
more information.
Rosemount devices are pre-instantiated with function blocks at the factory,
the default configuration for the Rosemount 5600 is listed below.
•
6 Analog Input Blocks (tag names AI 1300 through AI 1800)
Troubleshooting Table
Table 8-4 provides summarized maintenance and troubleshooting
suggestions for the most common operating problems. This section contains
Rosemount 5600 fieldbus troubleshooting information only.
Table 8-4. Rosemount 5600
troubleshooting table
Symptom
Corrective Actions
F
OUNDATION
fieldbus Card to Transmitter
Communication Fault
Verify Device Mode setting, should be Foundation fieldbus
(Parameter: ENV_DEVICE_MODE)
Restart method from Resource Block
Reboot transmitter (Cycle Power)
Level Measurement Failure
Check Power Supply
Check the transmitter configuration (Transducer Block)
Check that the mechanical installation is correct
Temperature Measurement Failure
Check temperature electrical installation
Check configuration (Transducer Block)
Restart the transmitter
Volume Measurement Failure
Restart transmitter
Check transmitter configuration using PC Based configuration Tool, Radar Master
No surface echo
Check signal strength
Restart transmitter
Tank Signal Clip Warning
Restart transmitter
Empty Tank/ Full Tank
Information of tank status
Configuration Reg Password Enabled
Information, Ready Write Data
DB Error/ Microwave Unit Error/ Configuration
Error/ Other Error
Restart transmitter
Call Rosemount Service Center
Download Application Software
Set database to default load Database default
SW Error/ Display Error/ Analog Out Error
Restart transmitter
Call Rosemount Service Center
F
OUNDATION
Fieldbus
Содержание 5600 Series
Страница 2: ......
Страница 4: ......
Страница 18: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 1 10 ...
Страница 64: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 2 46 ...
Страница 80: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 3 16 ...
Страница 99: ...Reference Manual 00809 0100 4024 Rev BA September 2005 4 19 Rosemount 5600 Series ...
Страница 100: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 4 20 ...
Страница 130: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 6 20 F OUNDATION Fieldbus ...
Страница 144: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series 7 14 2210 Display Unit ...
Страница 174: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series A 20 ...
Страница 185: ...Reference Manual 00809 0100 4024 Rev BA September 2005 B 11 Rosemount 5600 Series 5600APPROVAL03 EPS ...
Страница 186: ...Reference Manual 00809 0100 4024 Rev BA September 2005 Rosemount 5600 Series B 12 5600APPROVAL04 EPS ...
Страница 196: ...Reference Manual 00809 0100 4025 Rev BA April 2002 Rosemount 5600 Series C 8 F OUNDATION Fieldbus ...
Страница 204: ...Reference Manual 00809 0100 4025 Rev BA September 2005 Rosemount 5600 Series E 4 F OUNDATION Fieldbus ...
Страница 208: ...Reference Manual 00809 0100 4024 Rev BA March 2004 Rosemount 5600 Series Index 4 ...
Страница 209: ......