Rockwell Automation Publication 6300M-UM001A-EN-P - December 2021
15
Chapter 2 Install the Monitor
European Union Directive Compliance
The VersaView 6300M panel monitors for non-hazardous locations meet the
European Union Directive requirements when installed within the European
Union or EEA regions and have the CE marking. A copy of the declaration of
the conformity is available at
.
Connect peripheral cables to the appropriate I/O ports on the monitor. To
comply with EN 61326-1, see
Connect Peripheral Cables to the Monitor on
Installation Guidelines
Follow these guidelines to make sure that your monitor provides service with
excellent reliability.
•
When choosing the installation site, consider the following:
- The site must have sufficient power
- The site must be indoors and non-hazardous, except where the
monitor is rated for hazardous locations; see
- The site must not expose the monitor to direct sunlight
- The material for panel mounting must meet the criteria that are
described in
Prepare the Panel Cutout on page 18
•
The monitors can operate in a surrounding air temperature range of
0…50 °C (32…122 °F).
The surrounding air temperature must not exceed the maximum
temperature for your monitor, especially when the monitor is mounted
in an enclosure.
•
The monitors can be stored in a surrounding air temperature range of
-5…+60 °C (23…140 °F).
•
The relative humidity of the ambient air must be 20…90%
noncondensing at 0…40 °C (32…104 °F), and 20…80% noncondensing at
41…50 °C (105…122 °F).
IMPORTANT
VersaView 6300M panel monitors for hazardous locations are intended only
for USA and Canada applications.
ATTENTION:
This monitor is intended to operate in an industrial or control room
environment, which uses some form of power isolation from the public
low-voltage mains. Some monitor configurations cannot comply with the
EN 61000-3-2 Harmonic Emissions standard as specified by the EMC Directive of
the European Union. Obtain permission from the local power authority before you
connect any monitor configuration that draws more than 75 W of AC power
directly from the public mains.
All I/O cables must be used only indoors.
IMPORTANT
The monitor can operate at a range of extremes. However, the life
span of any electronic device is shortened if you continuously
operate the monitor at its highest rated temperature, which
includes the touch screen and LCD panel.