Replace Power Module Fuses
1. Remove the nut, lock washer, and washer from the top and bottom of the
fuse.
2. Remove the cables from the top and bottom of the fuse, and remove
another washer.
3. Install the new fuse, and replace cables and hardware in reverse order of
removal.
4. Torque all hardware to specifications (see
Figure 47 - Exploded View of Power Module Fuse
Inspect or Replace HECS
PowerFlex 6000 drives have three current sensors. For H-Frame drives they are
located inside the Power Module cabinet. For A-Frame and B-Frame drives
they are located inside the Transformer cabinet. Verify that the current sensor
wire connector is properly seated. Check for obvious signs of damage.
1. Unplug the Current Sensor Connector from the HECS.
ATTENTION:
Verify that the input circuit breaker feeding the drive is open.
Lock out and tagout the input circuit breaker before performing any work on
the drive or bypass units.
Washer
Lock washer
Nut
Fuse
ATTENTION:
To prevent electrical shock, disconnect the main power before
working on the drive. Verify that all circuits are voltage-free, using a hot stick
or appropriate high voltage-measuring device. Failure to do so may result in
injury or death.
Содержание Allen-Bradley PowerFlex 6000
Страница 10: ...10 Rockwell Automation Publication 6000 UM002G EN P August 2022 Preface Notes ...
Страница 82: ...82 Rockwell Automation Publication 6000 UM002G EN P August 2022 Chapter 4 Parameters and Function Codes Notes ...
Страница 134: ...134 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix C Preventative Maintenance Schedule Notes ...
Страница 136: ...136 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix D Torque Requirements Notes ...
Страница 148: ...148 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix E Spare Parts Storage Notes ...