118
Rockwell Automation Publication 6000-UM002G-EN-P - August 2022
Chapter 5 Preventative Maintenance and Component Replacement
Replace the eHIM
The integrated touch screen display (EHIM-T10CED4G) is located on the LV
Control cabinet door.
1. Disconnect the EtherNet/IP cable from PLC and the 3-pin power
connector (which contains the ground cable, and the 24V power supply
cable).
2. Remove and retain the eight mounting levers from the integrated touch
screen display.
3. Install the new integrated touch screen display inside the LV Control
cabinet door.
4. Reinstall all hardware and reconnect all cables in reverse order of
removal.
Replace LV Control Relays
1. Open the LV Control cabinet door.
Figure 65 - LV Control Relay Location
Ground cable
24V power supply
HMI
EtherNet/IP cable from PLC
3-pin power connector
Mounting lever (8)
IMPORTANT
Support the device from the outside of the door to prevent it from
falling through the front of the door.
ATTENTION:
Always perform Power Lockout procedure before servicing
equipment. Verify with a hot stick or appropriate voltage measuring device
that all circuits are voltage free. Failure to do so may result in severe burns,
injury, or death.
Содержание Allen-Bradley PowerFlex 6000
Страница 10: ...10 Rockwell Automation Publication 6000 UM002G EN P August 2022 Preface Notes ...
Страница 82: ...82 Rockwell Automation Publication 6000 UM002G EN P August 2022 Chapter 4 Parameters and Function Codes Notes ...
Страница 134: ...134 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix C Preventative Maintenance Schedule Notes ...
Страница 136: ...136 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix D Torque Requirements Notes ...
Страница 148: ...148 Rockwell Automation Publication 6000 UM002G EN P August 2022 Appendix E Spare Parts Storage Notes ...