2-16
Installation and Wiring
P46 Setting 8 - Two Wire Preset Speed Control (Analog Models Only)
This input mode is similar to Setting 1 except TB3 terminals 1, 2 and 8 provide
the function of preset speeds. Note: All analog functionality is disabled when using
this input mode setting.
Two-Wire Preset control
Figure 2.12
TB3 Terminal 2 and 8 Switch Definitions
Table 2.I
➊
Do not connect to TB3-4 in this mode.
➋
TB3 terminal 8 can be used to clear faults. See Figure 2.14 for details.
SW2 Position
TB3-8
SW1 Position
TB3-2
Speed Reference
Accel Rate
Decel Rate
Open (0)
Open (0)
Parameter 61
(Preset 0)
Parameter 30
Parameter 31
Open (0)
Closed (1)
Parameter 62
(Preset 1)
Parameter 30
Parameter 31
Closed (1)
Open (0)
Parameter 65
(Preset 4)
Parameter 69
Parameter 70
Closed (1)
Closed (1)
Parameter 66
(Preset 5)
Parameter 69
Parameter 70
1
23
4
56
7
8
Run Forward
Run Reverse
4 – 20 mA input
➊
Common
Common
SW1
SW2
➋
+10V
TB3
TB3-2 and TB3-8
See Table 2.I below
Содержание Allen-Bradley 160 SSC Series
Страница 12: ...1 6 Getting Started End of Chapter ...
Страница 58: ...5 20 Parameters and Programming End of Chapter ...
Страница 66: ...A 4 Specifications End of Chapter ...
Страница 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Страница 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Страница 82: ...C 6 CE Conformity End of Chapter ...
Страница 87: ......