5-2
Parameters and Programming
Important Reset Actions
You must set
P56 - [Reset Functions]
to 2 or cycle power after changing the setting
of
P46 - [Input Mode]
for the change to take effect.
If you reset to factory defaults, you cannot use the Program Keypad Module for
start or reverse control until it is selected using P46 setting 2.
Note:
P56 - [Reset
Functions]
must be set to 2 or power must be cycled for the change to take effect.
Important:
If you cycle power, you must wait a minimum of one minute for
the bus to discharge to zero to ensure the change has taken effect.
An
F48 - Reprogram Fault
can be cleared using the Program Keypad Module, Remote
Keypad Module or CopyCat Keypad Module stop button or by cycling input to
TB3-8.
Programming Example
The following is an example of the programming steps required to change a
Program Group
parameter setting. In this example,
P31 - [Decel Time]
is changed
from its factory default setting of 10.0 seconds to 2.2 seconds. Refer to Chapter 3
for an explanation of the Program Keypad Module display and programming keys.
Important:
To reset ALL values to original factory default settings, refer to
P56 - [Reset Defaults]
.
Action
Description
Keypad Display
1. To program the value of a
Program Group
parameter, enter the Program Group by
pressing the ESCape key. The Program Mode
Indicator will illuminate.
2. Press the Up/Down keys until the desired
parameter displays. In this case, press the Up
key until P31 - [Decel Time] displays.
3. Press SELect. The Program Mode Indicator
flashes, indicating that you can use the Up/Down
keys to change the parameter value.
4. Change the decel time value from the factory
default of 10.0 seconds to 2.2 seconds by
pressing the Down key until 2.2 displays.
Important:
Continuously holding the Up or
Down key will cause the value to increase or
decrease as long as the key is pressed.
5. When the desired value displays, press the
Enter key. This writes the new value to memory.
The Program Mode Indicator will stop flashing
and the display will flash once indicating that the
new value has been accepted.
Important:
If at any time (while in the program
mode) you wish to abort the editing process,
press the ESCape key. The original value of the
parameter will remain unchanged and you will
be exited from the Program mode.
Содержание Allen-Bradley 160 SSC Series
Страница 12: ...1 6 Getting Started End of Chapter ...
Страница 58: ...5 20 Parameters and Programming End of Chapter ...
Страница 66: ...A 4 Specifications End of Chapter ...
Страница 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Страница 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Страница 82: ...C 6 CE Conformity End of Chapter ...
Страница 87: ......