2-12
Installation and Wiring
P46 Setting 0 - Three-Wire Control (Factory Default)
This input mode provides a typical three wire control function where a momentary
start input will command the drive to start.
Three-Wire control – Factory Default
Figure 2.4
➊
Start input can be a momentary input.
P46 Setting 1 - Two-Wire Run Forward/Run Reverse Control
This input mode provides a typical two wire control function where a maintained
Run Forward or Run Reverse input will provide both a directional and start
command to the drive. Opening the Run Forward or Run Reverse input will
command the drive to stop in accordance with the
P34 - [Stop Mode]
setting. The
stop switch (TB3-7 and 8) is not required but can be wired as an Auxiliary Stop if
desired.
Two-Wire Run Forward/Run Reverse control
Figure 2.5
Stop
56
7
8
Common
Reverse
Start
➊
TB3
Note:
A contact closure on
terminals 7 and 8 is required
for the controller to respond
to a Start/Run command.
Stop
56
7
8
Common
Run Forward
Run Reverse
TB3
Note:
A contact closure on
terminals 7 and 8 is required
for the controller to respond
to a Start/Run command.
Содержание Allen-Bradley 160 SSC Series
Страница 12: ...1 6 Getting Started End of Chapter ...
Страница 58: ...5 20 Parameters and Programming End of Chapter ...
Страница 66: ...A 4 Specifications End of Chapter ...
Страница 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Страница 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Страница 82: ...C 6 CE Conformity End of Chapter ...
Страница 87: ......