4-2
Start-Up
Yes
No
Ready/Fault Indicating Panel Procedure
If you are using a Program Keypad Module, verify that
the Clockwise LED is illuminated. If you are using a
Ready/Fault Indicating Panel, verify that the Reverse input to
TB3 is in the Open position.
P01- [Output Frequency] will display. If drive has been previously
powered up, a different parameter may display.
Important:
To enable the Start and Reverse keys on the Program
Keypad Module, set P46 - [Input Mode] to 2 and cycle power (or
set P56 - [Reset Function] to 2). Refer to P56 in Chapter 5.
Program Keypad Module, Remote Keypad Module or
CopyCat Keypad Module Procedure
Set the frequency source to its minimum setting.
Issue a Stop command from the Program Keypad Module or TB3.
Issue a Start command from the Program Keypad Module
or TB3. Check the direction of motor rotation.
Drive fan will energize (some models).
If you are using a Program Keypad Module, verify that the
Clockwise LED is illuminated. If you are using a Ready/Fault
Indicating Panel, verify that the Reverse input to TB3 is in the
Open position.
Select P61 - [Preset Frequency 0] by removing all inputs to SW1,
SW2, and SW3 on TB3 (see Figure 2.21). The factory default
setting for P61 - [Preset Frequency 0] is 3 Hz.
Issue a Start command from the Program Keypad Module or
TB3. Drive fan will energize (some models).
Slowly increase the speed until the motor begins to turn.
Check the direction of motor rotation.
Issue a Stop command from the Program Keypad Module or TB3.
Direction of Motor Rotation Correct?
The green Ready indicator will illuminate.
Use inputs to TB3 to operate the drive.
Analog Signal Follower Model
Preset Speed Model
❶
Start-up is complete!
Disconnect and lock out all incoming power to
TB1 terminals R, S and T (L1, L2, and L3).
Switch any two of the three motor leads connected to TB2, terminals
U, V and W (T1, T2 and T3). Reconnect power. Check rotation.
continued from previous page
ATTENTION:
A DC Bus voltage may be present at the power
terminal blocks TB1 and TB2 for approximately three minutes after
power is removed from the drive.
❶
After successfully completing start-up, proceed to Chapter 5. If you need to change any factory
defaults, you will need a Program Keypad Module or other type of Communication Module.
Содержание Allen-Bradley 160 SSC Series
Страница 12: ...1 6 Getting Started End of Chapter ...
Страница 58: ...5 20 Parameters and Programming End of Chapter ...
Страница 66: ...A 4 Specifications End of Chapter ...
Страница 75: ...Accessories and Dimensions B 9 Drilling Template A Figure B 10 ...
Страница 76: ...B 10 Accessories and Dimensions Drilling Template B Figure B 11 ...
Страница 82: ...C 6 CE Conformity End of Chapter ...
Страница 87: ......