APPENDIX
Ed. 04/2012
83
APPENDIX
WARNINGS AND ERRORS
If the ACF is connected to a DDC, the warnings and errors will be displayed by the
DDC and also by the electronic circuit board; for further information see the
documentation regarding this issue.
Warnings and Errors
Two types of machine codes appear on the ACF60-00’s electronic circuit board display:
a) Warnings: identified by the green flashing letter
“u”
on the display, followed by the
code of the warning that is occurring.
b) Errors: identified by the green flashing letter “
E
” on the display, followed by the code of
the error that is occurring.
a) In the case of a WARNING event (
“
U
”
), the flashing letter
“
U
”
will appear on the
display followed by a number with corresponds to the nature of the event; when the
warning event has been corrected, the warning reported on the circuit board display
will be reset.
b) In the case of an ERROR event (
“E”
), the flashing letter “E” will appear on the display
followed by a number with corresponds to the nature of the event; The ERRORS do
not automatically reset and must be manually reset from menu 2 (see “RESETTING”
on page 35) or by cutting electrical power to the ACF (for more information see the
“TABLE OF OPERATING CODES“ reported below).
TABLE OF OPERATING CODES GENERATED BY THE ELECTRONIC
BOARD (version 3.021 firmware.)
E 0
FAULT ON RESET CIRCUIT OF FLAME CONTROL UNIT
CODE GENERATED BY
:
Fault on reset circuit of flame control unit.
RESET METHOD
:
Contact authorised Robur TAC.
U
1
MANUAL RESET OF THERMOSTAT, GENERATOR LIMIT TEMPERATURE
CODE GENERATED BY
:
High temperature detected by limit thermostat on body of generator
RESET METHOD
:
Reset limit thermostat manually: ACF operation will be restored automatically when the cause ceases.
E 1
MANUAL RESET OF THERMOSTAT, GENERATOR LIMIT TEMPERATURE
CODE GENERATED BY
:
U
1 code active for 1 hour, or
U
601 code generated 3 times in 2 hours of operation.
RESET METHOD
:
Contact authorised Robur TAC.
U
2
EXHAUST FUMES THERMOSTAT
CODE GENERATED BY
:
High temperature detected by exhaust fumes thermostat
RESET METHOD
:
Reset occurs automatically when the condition that generated the code ceases.
E 2
EXHAUST FUMES THERMOSTAT
CODE GENERATED BY
:
U
2 code active for 1 hour, or
U
602 code generated 3 times in 2 hours of operation.
RESET METHOD
:
Reset may be performed from the DDC (or from the S61 board via menu 2, parameter 1. If codes
U
2
and/or E 2 occur again, contact authorised Robur TAC.
Содержание GA ACF60-00
Страница 4: ......
Страница 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Страница 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Страница 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Страница 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Страница 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Страница 93: ...APPENDIX Ed 04 2012 89 ...
Страница 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Страница 95: ......