2.3 SETTING OF OPERATING PARAMETERS
The operations described require the basic knowledge of both the installed
appliance and the S61 electronic circuit board mounted on the ACF; You must be
familiar with this information before proceeding, which can be found in paragraph
2.2 ON-BOARD ELECTRONICS on page 30.
During the installation process, the ACF is configured by the installer to operate in
the most efficient manner for the type of system used. The operating parameters
can be changed after installation, but is not recommended if the operator does not
posses the necessary knowledge and experience.
To set new operating
parameters for the ACF60-00, go to paragraph 3.6 on page 50.
2.4 RESETTING
Errors may occur on the ACF60-00 which could cause the arrest of the unit for different
reasons; the error does not necessarily mean that there is a breakdown or that the ACF
has malfunctioned. The cause of the error could be temporary: air in the gas line or
temporary electrical blackout are some examples; in these situations, go to menu 2 of the
electronic circuit board to reset the ACF, returning it to normal operation.
The two reset options available in menu 2 are 0 and 1; Select E to exit the menu:
MENU OPTION
FOR RESETTING DUE TO:
SEEN ON THE DISPLAY
0
ARREST OF FLAME CONTROL UNIT
1
OTHER ERRORS
E
(EXIT FROM MENU)
Table 19 –
Menu for resetting operations
Option 0: reset the blocked flame control unit; this is also used to turn on the ACF for the
first time, see paragraph 2.1, page 29; or after a long shutdown period, see paragraph
“PROLONGED INACTIVITY”, page 38.
Requirements:
Accessibility to the electrical panel , see “Display and Knob
(encoder)”, page 32.
To reset the flame control unit, go to menu 2, as indicated in Access to the circuit board
menu’s on page 34, then:
Содержание GA ACF60-00
Страница 4: ......
Страница 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Страница 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Страница 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Страница 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Страница 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Страница 93: ...APPENDIX Ed 04 2012 89 ...
Страница 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Страница 95: ......