ACF60-00 – Installation, User’s and Maintenance Manual
16
Ed. 04/2012
ACF60-00 HT, ACF60-00 HT S – COOLING CAPACITY CORRECTION FACTORS
Table 7
–
ACF60-00 HT, ACF60-00 HT S – Cooling capacity multiplication correctional factors for external air
temperatures and water flow rates different from the nominal values reported in the table.
WATER DELIVERY TEMPERATURE °C
EXTERNAL AIR
TEMPERATURE
°C
5.0
7.0
10.0
12.5
14.0
0
1.02
1.02
1.02
1.02
1.03
2
1.02
1.02
1.02
1.02
1.03
4
1.02
1.02
1.02
1.02
1.03
6
1.02
1.02
1.02
1.02
1.03
8
1.02
1.02
1.02
1.02
1.03
10
1.02
1.02
1.02
1.02
1.03
12
1.02
1.02
1.02
1.02
1.03
14
1.02
1.02
1.02
1.02
1.03
16
1.02
1.02
1.02
1.02
1.03
18
1.02
1.02
1.02
1.02
1.03
20
1.02
1.02
1.02
1.02
1.03
22
1.02
1.02
1.02
1.02
1.03
24
1.02
1.02
1.02
1.02
1.03
26
1.01
1.02
1.02
1.02
1.03
28
1.01
1.02
1.02
1.02
1.03
30
1.01
1.02
1.02
1.02
1.03
32
0.99
1.02
1.02
1.02
1.03
34
0.96
1.01
1.01
1.01
1.02
35
0.94
1.00
1.00
1.01
1.02
36
0.92
0.99
1.00
1.00
1.02
38
0.87
0.97
0.99
0.99
1.01
40
0.82
0.93
0.97
0.98
1.00
42
—
0.88
0.94
0.97
0.99
44
—
0.82
0.91
0.95
0.97
46
—
—
0.86
0.92
0.95
48
—
—
0.80
0.87
0.91
50
—
—
—
0.81
0.86
Содержание GA ACF60-00
Страница 4: ......
Страница 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Страница 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Страница 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Страница 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Страница 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Страница 93: ...APPENDIX Ed 04 2012 89 ...
Страница 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Страница 95: ......