Section GENERAL INFORMATION AND TECHNICAL SPECIFICATIONS
Ed. 04/2012
13
ACF60-00 TK, ACF60-00 TK S - TECHNICAL SPECIFICATIONS
SIZE
UNIT
ACF60-00
TK
ACF60-00
TK S
OPERATIONAL CHARACTERISTICS
NOMINAL HEAT CAPACITY AT THE BURNER
(1)
NOMINAL
EFFECTIVE
kW
25.30
25.03
COOLING CAPACITY
(2)
kW
17.72
CHILLED WATER FLOW RATE
NOMINAL
MINIMUM
MAXIMUM
L/hr
2770
2500
3200
m
3
/h
GAS CONSUMPTION NAT. GAS
(3)
L.P.G.
(4)
NOMINAL
EFFECTIVE
NOMINAL
EFFECTIVE
kg/hr
2.68
2.65
1.96
1.94
NOISE LEVEL
(5)
(6)
at 10 meters
MAXIMUM
dB(A)
54
49
FUNCTIONAL RANGE (T
OUTSIDE AIR
)
MINIMUM
MAXIMUM
°C
-12
+45
ACF INTAKE WATER TEMPERATURE
MAXIMUM
°C
+45
OUTLET WATER TEMPERATURE
(7)
MINIMUM
°C
+3
ELECTRICAL CHARACTERISTICS
VOLTAGE
V, phases,
Neutral, Hz
230 1N 50
TOTAL ELECTRICAL LOAD
(8)
W
900
930
WATER CONNECTIONS
WATER DELIVERY AND RETURN
“
1 ¼ “F
GAS
“
¾ “F
ACF INTERNAL PRESSURE DROP
(9)
NOMINAL
bar
0.29
MAXIMUM WORKING PRESSURE
bar
4
MAXIMUM FILLING PRESSURE
bar
3
PHYSICAL SPECIFICATIONS
OPERATIONAL WEIGHT
kg
350
380
INTERNAL WATER CAPACITY OF ACF
L
3
WIDTH
850
DEPTH
1230
DIMENSIONS
(10)
HEIGHT
mm
1290
1540
(9)
Table 4
–
ACF60-00 TK and ACF60-00 TK S Technical Specifications
Remarks
(1)
Nominal conditions: 1013 mbar, 15 °C; Effective conditions: 1000 mbar, 20 °C
(2)
Nominal running conditions: external air temperature 35°C; chilled water temperature - delivery 7.2 °C – return 12.7 °C. For
conditions other than the nominal conditions, apply the cooling capacity correction factors seen in
Table 5
, page 14.
(3)
PCI 34.02 MJ/m
3
(1013 mbar – 15 °C).
(4)
PCI 46.34 MJ/kg
(5)
A reduction in RPM of the fan (air delivery) is required for external air temperatures less than 33°C.
(6)
Sound source rested on a reflective surface.
(7)
To be eventually set only by personnel Robur. Minimum Temperature Factory Set = 4,5°C
(8)
±
10% in relation to the power supply and tolerance on the power draw of the electrical motors.
(9)
Nominal running conditions: return water temperature 12.7°C; delivery 2770 L/hr. For deliveries different from the nominal, please
refer to
Figure 4
, page 24.
(10)
Height of the silenced ventilation, ACF TK version, complete with fan nozzle.
Содержание GA ACF60-00
Страница 4: ......
Страница 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Страница 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Страница 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Страница 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Страница 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Страница 93: ...APPENDIX Ed 04 2012 89 ...
Страница 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Страница 95: ......