Section PLUMBING INSTALLER
Ed. 04/2012
41
Also avoid installing the unit in corners to avoid the amplification of the noise due to
reverberation.
Position the appliance so as to maintain
minimum clearances
from combustible
surfaces, walls or other appliances, as illustrated in Figure 13.
Minimum clearances are are required to make maintenance possible
Do not install any cover or obstruction to the evacuation of the air issuing from the fan.
When deciding on the installation position, especially if multiple units are used, consider
that each unit requires 11,000 m
3
/h of air for heat exchange with the finned battery. Make
sure that the installation and position allow for sufficient flow of air to the batteries and
prevent the air issuing from the fans recirculating, which would reduce the efficiency of the
units and force them to switch off.
Install the ACF away from water falling from rain gutters or similar.
If the ACF is installed on a terrace or on a roof, it must be done so that the exhaust from
the fans does not exit near the external air intakes of the building. in any case, avoid the
intake of contaminated or hot air coming from flues, chimneys, vents and others by the
ACF.
8
0
0
6
0
0
450
450
8
0
0
6
0
0
450
450
450
Figure 13 –
Minimum distances to respect for the correct functioning of the ACF.
FRONT
FRONT
FRONT
Содержание GA ACF60-00
Страница 4: ......
Страница 6: ...ACF60 00 Installation User s and Maintenance Manual 2 Ed 04 2012 ...
Страница 56: ...ACF60 00 Installation User s and Maintenance Manual 52 Ed 04 2012 ...
Страница 86: ...ACF60 00 Installation User s and Maintenance Manual 82 Ed 04 2012 ...
Страница 91: ...APPENDIX Ed 04 2012 87 APPENDIX DECLARATION OF CONFORMITY ...
Страница 92: ...ACF60 00 Installation User s and Maintenance Manual 88 Ed 04 2012 ...
Страница 93: ...APPENDIX Ed 04 2012 89 ...
Страница 94: ...ACF60 00 Installation User s and Maintenance Manual 90 Ed 04 2012 ...
Страница 95: ......