4 Operation
MANUAL TME400-VCF · EN04 · 2019 March 26th
61
A22
Digital output 2
pulse width
A22 digital output 2 pulse width
20 ms
125 ms (default)
250 ms
Coor-
dinate
Name
Modbus
register
Modbus
access
Protec-
tion
Data
type
Min. Max.
Default Unit
A01
Standard volume
300
W
E
unit32
0
99999999
0
m3
A02
Operating volume
302
W
E
unit32
0
99999999
0
m3
A03
Standard volume error
304
W
E
unit32
0
99999999
0
m3
A04
Operating volume error
306
W
E
unit32
0
99999999
0
m3
A05
Uncorrected operating
volume
308
W
E
unit32
0
99999999
0
m3
A06
Volume Start/Stop
310
W
N
unit32
0
99999999
0
m3
A07
Volume Reset
312
W
N
unit32
0
99999999
0
m3
A10
Meter factor
500
W
E
string12
*
*
1000.0 I/m3
A11
Output pulse factor
506
W
E
float
0.01
100
1.0
I/m3
A12
Meter factor corrected
508
R
A
float
-
-
1.0
I/m3
A20
Display factor
510
W
E
menü16
0
4
2
A21
Digital output 2 mode
511
W
E
menü16
0
1
0
A22
Digit. output 2 pulse width 512
W
N
menü16
0
2
1
ms
4.3.3.2.
Flow rate
Coordi-
nate
Name
Description
B01
Standard flow rate
Flow value under standard conditions (see above)
B02
Operating flow rate
Flow rate under current operating conditions
B03
Frequency
Unchanged output value, frequency of Sensor 1.
B05
Min. flow rate
An alarm is generated below this flow rate
B06
Max. flow rate
An alarm is generated above this flow rate
B10,
B11,
B12,
B13,
B14,
B15
Coefficients:
A-2, A-1, A0, A1, A2
Max. operating point
deviation
Z26: If the characteristic correction is deactivated, the additional pa-
rameters are not visible and cannot be adjusted. If a characteristic
correction is activated (see Z26 below), a correction takes place with
the factors in:
B10: Factor for the characteristic correction
B11: Factor for the characteristic correction
B12: Factor for the characteristic correction
B13: Factor for the characteristic correction
B14: Factor for the characteristic correction
B15: If the deviation of the corrected from the uncorrected character-
istic at an operating point (or a range) is more than the adjusted
Содержание TME400-VC
Страница 6: ......
Страница 47: ...2 Installation MANUAL TME400 VCF EN04 2019 March 26th 41 Ex version...
Страница 48: ...2 Installation MANUAL TME400 VCF EN04 2019 March 26th 42 Ex version with current module...
Страница 49: ...2 Installation MANUAL TME400 VCF EN04 2019 March 26th 43 Non Ex version...
Страница 109: ...APPENDIX MANUAL TME400 VCF EN04 2019 March 26th 103 D Seal diagrams Will be added as soon as available...
Страница 111: ...MANUAL TME400 VCF EN04 2019 March 26th 105...