24.
L
WARNING! Danger of a faulty release!
To activate the system: Switch the blocking switch (Fig. 17 /arrow) to "Agent
connect [not blocked]" (Fig. 17 /
Ⅰ
).
ð
The system is ready for operation and release.
Chapter 5.3 „Installation and commissioning of
additional electrical devices” on page 38
5.2.3
Temperature indicator
Check that the temperature indicator
(65 °C) is in a proper state (Fig. 18 ). The
temperature indicator is on the front cover.
If the temperature indicator is dark
(Fig. 19 ), it is possible that electrical com-
ponents have been damaged or that the
tank has a leak due to the increased pres-
sure caused by an increased temperature.
Contact the Authorized Distributor if the
temperature indicator is dark in color and
have the system replaced.
5.2.4
Language setting for display and operation
The system can communicate in "German"
and "English". "German" is pre-set by the
manufacturer but can be changed to "Eng-
lish" via a DIP switch (Fig. 20 ). Proceed as
follows to make the changeover:
1.
To block the system: Switch the blocking switch (Fig. 21 /arrow) to "Agent dis-
Ⅱ
).
2.
Disconnect the system from the superordinate system: Remove the
CAN bus
connecting cable (Master/Slave)
and power supply cable.
Fig. 18: Temperature indicator light:
Temperature is okay.
Fig. 19: Temperature indicator dark:
Notice, temperature was exceeded!
Fig. 20: Language setting
Mounting and installation
Operating Instructions / DET-AC III Slave / 916007 / 05-2016 / en_US
35
Содержание 7338.321
Страница 82: ...Appendix Appendix Operating Instructions DET AC III Slave 916007 05 2016 en_US 82 ...
Страница 84: ...Operating Instructions DET AC III Slave 916007 05 2016 en_US 84 ...
Страница 85: ......
Страница 86: ...Ì916007 Î ...