3.
Peel off the transparent protective film.
4.
Switch the DIP switch "4" from position "OFF" (German) to "ON" (English).
5.
Stick the protective film on again.
6.
Put the system in service again.
5.2.5
Checking the failure and alarm function
The checking of the failure and alarm
function is performed at the superordi-
nate system.
The system is ready for operation when the
door is closed: The green LED lights up
and
„State OK”
is shown in the display. If
this is not the case, actuate the upper
[Reset]
button. The green LED then blinks twice and messages that are still pending
are reset.
INFORMATION
Switch the system into the revision state for inspection. Transmissions are blocked
by this.
5.2.5.1
Door contact switch
By opening a door to the protected cabinet which is equipped with a door contact
switch, the message
„Blocking by door cont.”
is generated and the yellow LEDs lit
up.
By removing the door contact plug on the rear side of the system, the door contact
switch is deactivated. The message
„Failure door contact”
is also shown in the dis-
play.
Remount the door contact switch and activate the system using the upper
[Reset]
button.
The check must be performed for each of the door contact switches that are
installed.
Fig. 21: Blocking switch
Fig. 22: [Reset] button
Mounting and installation
Operating Instructions / DET-AC III Slave / 916007 / 05-2016 / en_US
36