Maintenance every two years (Authorized Distributor)
The Authorized Distributor must perform maintenance work to the system at least
every two years.
A total service life of 10 years is set for the integrated detectors employed in the
system if used in dry areas free from combustible dust and corrosive atmosphere.
Regular inspections, maintenance, cleaning and calibration where applicable are
prerequisites for this.
In isolated cases, shorter periods for changes may be required depending on
ambient conditions or fire detector type.
The maintenance tasks are documented in the checklists that are intended to serve
this purpose.
10.2.1
Checking for proper installation
Check whether the system is installed in the upper third.
Check and report horizontal installation using a spirit level.
10.2.2
Checking for external damage
Check all connections and the system itself for external damage.
10.2.3
Recording the WA No. / Part No. / F. No.
Read the factory order number (WA No.), the part number (Part No.) and the pro-
duction number (F. No.) of the system on the labels and report them in the service
report. The labels are on the housing cover and on the rear of the system.
10.2.4
Recording the date of the current maintenance / inspection
Fill out the report for the date of the current and last maintenance by hand or read it
out via the Maintenance Program
Chapter 9.6 „Customer data” on page 58
.
10.2.5
Recording the current version
Refer to the Maintenance Program for the current version states
.
● Firmware version
● Control panel version
● BIOS version
Repairs
Operating Instructions / DET-AC III Slave / 916007 / 05-2016 / en_US
66