4.
Connect and activate the system with the
CAN bus connecting cable (Master/
Slave)
and the power supply cable to a superordinate system.
5.
Check whether the LED "Failure" lights up on the superordinate system and
whether the message
„Failure extinguishing output”
is shown in the display.
6.
Make the settings for using door contact switches
7.
Make the necessary settings for the combination of "DET-AC III Master" and
"DET-AC III Slave"
Chapter 5.3.4 „Combination of systems” on page 43
.
8.
Deactivate the system at the superordinate system using the battery button.
9.
Remove the
CAN bus connecting cable (Master/Slave)
and power supply
cable.
10.
Install guide rails laterally to support the system.
11.
Fit the system with the guide rails via the guide rail noses to the rear section of
the cabinet.
12.
Insert the system horizontally on the guide rails until the stop at the front panel.
13.
Align the system horizontally using a spirit level.
14.
Fasten the system at the front panel in the 19" frame using the screws pro-
vided, including the black plastic washers. The holes for fastening are on the
right and left outer side of the front panel.
15.
Tighten the guide rail screws laterally.
16.
To commission the system, connect the
CAN bus connecting cable (Master/
Slave)
and the power supply cable to a superordinate system and actuate the
"Battery ON" button there.
17.
Connect the mains supply at the superordinate system.
18.
Connect door contact switch/switches (optional)
19.
Connect alarm elements (optional).
20.
Connect the Monitoring System CMC (optional)
.
21.
Assign potential-free contacts (optional)
Chapter 5.3.1 „Potential-free con-
22.
Import the set parameters using the Maintenance Program
23.
Check the failure and alarm functions
Chapter 5.2.5 „Checking the failure
and alarm function” on page 36
Mounting and installation
Operating Instructions / DET-AC III Slave / 916007 / 05-2016 / en_US
34
Содержание 7338.321
Страница 82: ...Appendix Appendix Operating Instructions DET AC III Slave 916007 05 2016 en_US 82 ...
Страница 84: ...Operating Instructions DET AC III Slave 916007 05 2016 en_US 84 ...