Copyright © 2008 by Lucky Distributing
Revision 2.0 updated 11/05/2008
8
MAIN CONTROL BOARD
1
2
3
4 5 6 7 8 9
AC Voltage Side
I
110VAC
60Hz
II
Combustion
Fan
III
Convection
Fan
IV
Ignition Element
V
Auger
Motor
VI
Open
VII
Reserved
NOTE:
A common error made when swapping out a
control board is to cross the auger motor and igniter leads.
A symptom of this is the auger motor turning continually
with no pause for the 12-minute duration of the ignition
element time, resulting in a very full burn pot. The igniter
will pulse on and off during the same period.
DC Voltage Side
1
HAL-IC Combustion Motor Regulator
(silver
bullet looking item mounted just above the air intake tube.
There is another lead on this component that is also attached
to the combustion fan).
2
User Control Interface
3
Optional Remote Thermostat
(leave open if no thermostat present)
4
Air
Sensor
5
Low Limit Sensor
(error flashing
immediately following
startup cycle may
indicate a disconnected lead or a failure of this
component. Other possible triggers are a first-time-fill
of the hopper, open hopper lid or recent empty hopper
– restart stove to see if error recurs).
6
High Limit Sensor
(error flashing
during
startup cycle may indicate a
disconnected lead or a failure of this component)
7
open
8
open
9
open
I
II
III
IV V VI VII
Содержание INTEGRA II
Страница 1: ...Copyright 2008 by Lucky Distributing Revision 2 0 updated 11 05 2008 1...
Страница 32: ...Copyright 2008 by Lucky Distributing Revision 2 0 updated 11 05 2008 32 CONTROL FLOW CHART...
Страница 36: ...Copyright 2008 by Lucky Distributing Revision 2 0 updated 11 05 2008 36...
Страница 37: ...Copyright 2008 by Lucky Distributing Revision 2 0 updated 11 05 2008 37...