System 2 - SOLAR WATER HEATING WITH SUPPLEMENTARY HEATING

The controller calculates the temperature differential  between 

collector sensor S1 and storage cylinder sensor S2. If the differ-

ential exceeds or is equal to the set activation temperature dif-

ferential (

DT O

), relay 1 activates the solar pump and the storage 

cylinder is charged until the deactivation temperature differen-

tial (

DT F

) or maximum storage cylinder temperature (

S MX

) is 

reached.

Sensor S3 is used for the thermostat function for supplementary 

heating, activated by relay 2, or for excess heat dissipation when 

thermostat activation temperature (

AH O

) is reached.

This function can be combined with three adjustable time 

bands.

Sensor S3 can be used as a reference sensor for the thermal dis-

infection function (

OtD

) or for the storage cylinder safety deacti-

vation function (

OSEM

).

Optionally, sensor S4 can be used for measurement purposes. If 

the thermal energy metering function (

OHQM

) is activated, sen-

sors S4 and 

VFD

 can be used as flow and return sensors.

VBus

PWM

VFD

R2

S1

S2

R1

S3/TSS

S4/VFD/TMAN

S4/VFD/TRIT

Fig. 3

Relay out-

puts

Control differential

Notes

R1

DT (S1-S2)

Solar pump (P1)

R2

TE (S3)

Circulation pump (P2)

Sensor-input

Description

S1

Collector temperature

S2

Storage cylinder bottom temperature

S3

Storage cylinder top temperature

S4/VFD

Collector flow/return temperature

(optional, view-only)

Содержание SUN 1 PLUS 2 RS

Страница 1: ...cod 20100537 rev 2 09 2015 SUN 1 PLUS 2 RS EN INSTALLATION INSTRUCTIONS...

Страница 2: ...res also stock any original spare parts that might be required This manual contains important instructions and precautions that must be observed to ensure the trouble free installation and efficient f...

Страница 3: ...tion activation time display 17 19 CONTROL PARAMETERS 18 19 1 System layout selection 18 19 2 T settings 18 19 3 Pump control 18 19 4 Maximum storage cylinder temperature 19 19 5 Option storage cylind...

Страница 4: ...st another copy from your local Technical Assis tance Service R 9 9This control panel is designed and made for use with boilers generating hot water up to 110 C and must be used exclu sively for this...

Страница 5: ...lets you scroll back through displayed parameters access the parameter setting viewing area and decrement con trol parameter setpoints Button 3 OK set lets you edit control parameters and confirm new...

Страница 6: ...vated Frost protection function active Manual mode relay 1 ON Manual mode relay 2 ON Manual mode relay 1 2 OFF Sensor fault 8 SYSTEM LAYOUT SCHEMATIC The system layout area displays a schematic of the...

Страница 7: ...ture sensors 1 x VFD sensor Data communication VBus Vbus current level 35 mA PWM frequency 512 Hz PWM voltage 10 5 V 10 WIRING DIAGRAM Fuse VBus Grid terminals Consumer terminals Sensor terminals Safe...

Страница 8: ...ownwards to remove it from the controller Cross head screw Mark the top fixing point on the mounting plate or wall Drill the hole and fit the plug and fixing screw supplied with the controller Display...

Страница 9: ...off 17 neutral wire 13 earth ground wire Water connections R2 16 live wire control switch for switching pump on off 15 neutral wire 14 earth ground wire 1 1 A 240V 1 1 A 240V R1 R2 L R1 N N 9 1 0 2 18...

Страница 10: ...he PWM socket are used as control outputs for a pump with a PWM control input The two right pins are not used PWM 1 2 1 PWM output 1 control signal 2 1st PWM output GND 15 PUTTING INTO SERVICE Electri...

Страница 11: ...rve for an HE solar pump PRIS PWM curve for an HE heating pump To reduce the frequency of high efficiency pump starts the controller automatically extends its functioning when no speed control signal...

Страница 12: ...ture display TS x x Storage cylinder 1 temperature display TSTT x x x Storage cylinder 1 top temperature display TDIS s Thermal disinfection temperature display S3 x x Sensor 3 temperature display S4...

Страница 13: ...rotection option CFR x x x Collector 1 frost protection temperature OTC x x x Tube collector function TCST x x x Activation time TCEN x x x Deactivation time TCRU x x x Run time TCIN x x x Inactive ti...

Страница 14: ...lay 2 manual mode LANG x x x Language UNIT x Unit of measurement for temperature RESE x Reset function PROG XX XX Program number VERS X XX Version number 9 9See the corresponding section for the activ...

Страница 15: ...Shows the current temperature of the collector 18 3 Storage cylinder temperature display TS TSTB TSTT TDIS Storage cylinder temperature Display range 40 260 C Shows the temperature measured in the st...

Страница 16: ...e starts to flash and the count is reset to zero Press button 3 again to confirm To cancel the reset press button 3 for 5 seconds The controller switches to initial display mode kWh MWh Thermal energy...

Страница 17: ...heating period is active remaining time in hours and minutes is counted down and displayed as DDIS 18 10 Thermal disinfection activation time display SDIS Activation time display Display range 00 00...

Страница 18: ...ontroller The pump is activated as soon as the activation differential DT 0 is reached If the temperature differential is les than the set deactivation temperature differential DT F the controller dea...

Страница 19: ...display Note The controller incorporates a safety deactivation function that stops circulation to the storage cylinder or buffer tank if the temperature of the heat transfer medium reaches approximat...

Страница 20: ...ystem cooling function OCC is set ON the controller mon itors collector temperature and cools the collector if necessary If maximum storage cylinder temperature is reached the solar pump is deactivate...

Страница 21: ...protection function is activated for the collector associated with that parameter The frost protection function activates the heating circuit between the collector and the storage heater to prevent i...

Страница 22: ...liday cooling is activated the symbols and flashing appear on the display 19 12 Tube collector option OTC Tube collector option Setting range ON OFF Default setting OFF TCST Tube collector function ac...

Страница 23: ...vals t1 t2 and t3 are available for activation and deactivation Example If the function must only be activated between e g 6 00 and 9 00 set t1 O to 6 00 and set t1 F to 09 00 The thermo stat function...

Страница 24: ...ime for which relay R2 is activated to run the circulation pump between the boiler and the storage cylinder When this function is active the time DDIS appears among the view only parameters and shows...

Страница 25: ...nMX parameter lets you set a maximum speed for the pump 9 9Note If electrical equipment with no speed control e g valves is used set the relay speed to 100 or set the pump control to OnOF to deactivat...

Страница 26: ...t dis played if MEDT is set to 0 or 3 Setting range 20 70 Default setting 45 Note If system layout 3 has been selected and the OHQM func tion activated thermal energy metering is interrupted as soon a...

Страница 27: ...the ODB function is later deactivated 19 27 Period activation condition tDTO Period activation condition Setting range 1 100 s Default setting 60 s Parameter tDTO can be used to set the period for whi...

Страница 28: ...unit of measurement for temperature Selection F C Default setting C This parameter lets you select the unit of measurement in which you want to display temperatures and temperature differentials You c...

Страница 29: ...reference sensor for the storage cyl inder safety deactivation function OSEM If the thermal energy metering function OHQM is activated sensors S4 and VFD can be used as flow and return sensors 9 10 V...

Страница 30: ...tial 0 5 19 4 K DT S Nominal temperature differential 1 5 30 10 K RIS Boost 1 20 2 K PUM Pump control OnOF PULS PSOL PRIS PSOL nMN Minimum speed 30 to 100 30 nMX Maximum speed 30 to 100 100 S MX Stora...

Страница 31: ...ring flow rate OFF 1 2 2 MEDT Type of frost protection 0 3 1 MED Level of frost protection 20 70 45 ODB Drainback function ON OFF OFF tDTO Period activation condition 1 100 60 s tFLL Filling time 1 30...

Страница 32: ...rmostat activation temperature AH O is reached This function can be combined with three adjustable time bands Sensor S3 can be used as a reference sensor for the thermal dis infection function OtD or...

Страница 33: ...tivation temperature differential 0 5 19 4 K DT S Nominal temperature differential 1 5 30 10 K RIS Boost 1 20 2 K PUM Pump control OnOF PULS PSOL PRIS PSOL nMN Minimum speed 30 to 100 30 nMX Maximum s...

Страница 34: ...N OFF OFF PDIS Monitoring period 0 to 30 0 to 24h 01 00 hh TDIS Disinfection temperature 0 95 60 C DDIS Disinfection duration 00 00 23 59 01 00 hh mm SDIS Wait time 00 00 24 00 00 00 hh mm GFD Grundfo...

Страница 35: ...erature CMX is reached relay 1 activates the solar pump and relay 2 activates the 3 way valve to dissipate excess heat via a heat dissipater For safety reasons excess heat is dissipated only until the...

Страница 36: ...SOL PRIS PSOL nMN Minimum speed 30 to 100 30 nMX Maximum speed 30 to 100 100 S MX Storage cylinder 1 maximum temperature 4 95 60 C OSEM Storage cylinder safety deactivation ON OFF OFF EM Collector 1 s...

Страница 37: ...rcuit filter clogged Clean the filter Non return or shut off valves faulty Replace the faulty components The pump comes on too late Activation temperature differential Ton too high Change Ton and Toff...

Страница 38: ...differential between storage cylinder and system Create a siphon in the highest pipe Non return valves faulty Replace the faulty components The pump runs for a long time at night when the system is ac...

Страница 39: ...39...

Страница 40: ...el 0442630111 Fax 044222378 www riello it The manufacturer strives to continuously improve all products Appearance dimensions technical specifications standard equipment and accessories are therefore...

Отзывы: