25
19.19
Option: remaining monitoring time
CDIS
: Remaining monitoring time
Display range: 0 ... 30:0 ... 24 (dd:hh)
Once values have been entered for parameters
PDIS
,
TDIS
and
DDIS
, the time remaining to the end of monitoring is displayed
in the
CDIS
parameter.
If this period finishes, but a disinfection activation delay has
been set, the
SDIS
parameter flashes and shows the time re-
maining to activation. On completion of the disinfection cycle,
parameters
DDIS
and
SDIS
are hidden and only
CDIS
remains vis-
ible.
During the
CDIS
period, if storage cylinder top temperature stays
above
TDIS
for the time
DDIS
, the value of
CDIS
is reset equal to
the entire period
PDIS
19.20
Minimum speed
nMN
: Minimum speed
Setting range: (10) 30 ... 100 %
Default setting: 30 %
nMN if ODB activated: 50 %
Thermal energy metering can be implemented in two ways:
with a fixed flow rate or with a Grundfos Direct Sensor™ VFD.
9
Note!
If devices with no speed control (e.g. valves) are con-
nected, minimum relay speed must be set at 100 %.
nMX
: Maximum speed
Setting range: (10) 30 ... 100 %
Default setting: 100 %
The
nMX
parameter lets you set a maximum speed for the pump.
9
Note!
If electrical equipment with no speed control (e.g.
valves) is used, set the relay speed to 100 % or set the pump
control to OnOF to deactivate speed control.
19.21
Grundfos Direct Sensor™ activation
GFD
: Grundfos Direct Sensor™ activation
Selection: OFF, 12, 40, 40F
Default setting: OFF
Activation of a digital sensor to measure flow rate and meter
thermal energy.
OFF
no Grundfos Direct Sensor™
12
VFD 1 - 12 (only in water/propylene glycol mixes)
40
VFD 2-40
40F
VFD 2-40 Fast (only in water)
19.22
Thermal energy metering
OHQM
: Thermal energy metering
Setting range: ON, OFF
Default setting: OFF
When the
OHQM
function is activated, the quantity of heat pro-
duced can be calculated and displayed. Thermal energy meter-
ing
OHQM
can be implemented in two ways: with a fixed flow
rate or with a Grundfos Direct Sensor™ VFD.
19.23
Thermal energy metering with fixed flow rate
Thermal energy metering can be implemented with the aid of
a flow meter. To implement thermal energy metering, proceed
as follows:
− Set the flow rate shown by the flow meter in parameter
FMAX
when the pump is running at maximum speed
− Specify the desired heat transfer medium and percentage
of anti-freeze in the parameters
MEDT
and
MED%